Worked example
Example: Ganapathy: 75 MMBtu/h gas, 10 % excess air. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Heat input (HHV basis) | 21.980 MW |
| Fuel (Ganapathy Table 2.4: dry air per MMBtu fired, lb) | Natural gas (730) |
| Excess air | 10.000 % |
| Fuel higher heating value | 46.520 MJ/kg |
| Air humidity (kg water per kg dry air) | 0 g/kg |
| Ash in the fuel, as fired (subtracted from the flue gas) | 0 % |
Applying the formula below gives:
| Result | Value |
|---|---|
| Theoretical dry air per unit heat | 313.84 kg/GJ |
| Dry combustion air | 27.318 t/h |
| Wet combustion air | 27.318 t/h |
| Fuel | 1.7010 t/h |
| Flue gas (wet air + fuel) | 29.019 t/h |
| Wet air per kg fuel | 16.060 kg/kg |
Open this example in the calculator and change any input.
Formula
\(A_{SI} = A\ \mathrm{lb/MMBtu} \to \mathrm{kg/J}, \quad W_a = Q\,A_{SI}\,(1 + EA), \quad W_{aw} = W_a(1 + \omega), \quad W_f = \frac{Q}{HHV}\)
\(W_g = W_{aw} + W_f\,(1 - A_f), \quad \frac{W_{aw}}{W_f} = A_{SI}\,(1 + EA)(1 + \omega)\,HHV\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(Q\) | Heat input (HHV basis) | W |
| \(A\) | theoretical dry air per MMBtu fired for the fuel chosen (Ganapathy Table 2.4) | lb/MMBtu |
| \(A_f\) | ash in the fuel as fired | - |
| \(EA\) | Excess air | - |
| \(HHV\) | Fuel higher heating value | J/kg |
| \(\omega\) | Air humidity (kg water per kg dry air) | kg/kg |
| \(A_{SI}\) | Theoretical dry air per unit heat | kg/J |
| \(W_a\) | Dry combustion air | kg/s |
| \(W_{aw}\) | Wet combustion air | kg/s |
| \(W_f\) | Fuel | kg/s |
| \(W_g\) | Flue gas (wet air + fuel less ash) | kg/s |
| \(W_{aw}/W_f\) | Wet air per kg fuel | kg/kg |
Method and standards
Ganapathy's MMBtu method.
Where it is used
- Fan and duct sizing.
- Quick checks of boiler and heater data sheets.
Common mistakes
- Using LHV heat input with A on HHV basis.
- Forgetting air moisture.
Assumptions and limits
- HHV basis. The ash entered is subtracted from the flue gas; leave it 0 for gas and oil.
- The HHV entered is not checked against the fuel class chosen for \(A\); keep them consistent (a gas \(A\) with a coal HHV gives a wrong fuel flow).
References
- Ganapathy
- Steam Plant Calculations Manual
- 2nd ed. (Marcel Dekker, 1993)
- Q2.10 and Table 2.4 (combustion constant A)
Questions and answers
Why is air per unit heat nearly constant?
Heat release and oxygen demand both scale with carbon and hydrogen burnt; fossil fuels need 720–780 lb of air per MMBtu.
How accurate is it?
Good enough for fan and duct sizing, Ganapathy notes, when the fuel analysis is unknown.
What does A mean in SI?
730 lb/MMBtu natural gas is about 314 kg of air per GJ fired.
Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.