Worked example
Example: 80 MW with 4 of 6 burners, 20 MW max, 6 MW min. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Total boiler heat input (same GCV or NCV basis as the burner ratings) | 80.000 MW |
| Burners in service | 4.0000 - |
| Burner maximum rating | 20.000 MW |
| Burner minimum stable firing | 6.0000 MW |
Applying the formula below gives:
| Result | Value |
|---|---|
| Heat input per burner | 20.000 MW |
| Burner load, share of maximum | 100.00 % |
| Burner turndown ratio | 3.3333 |
| Lowest boiler firing with these burners | 24.000 MW |
| Highest boiler firing with these burners | 80.000 MW |
Open this example in the calculator and change any input.
Formula
\(\dot Q_b = \frac{\dot Q}{n} \qquad \lambda = \frac{\dot Q_b}{\dot Q_{max}} \qquad TD = \frac{\dot Q_{max}}{\dot Q_{min}} \qquad \dot Q_{lo} = n\,\dot Q_{min} \qquad \dot Q_{hi} = n\,\dot Q_{max}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\dot Q\) | total heat input | W |
| \(n\) | burners in service | – |
| \(\dot Q_{max}\) | burner maximum rating | W |
| \(\dot Q_{min}\) | burner minimum stable firing | W |
| \(\dot Q_b\) | heat input per burner | W |
| \(\lambda\) | burner load | – |
| \(TD\) | turndown ratio | – |
| \(\dot Q_{lo}\) | lowest boiler firing | W |
| \(\dot Q_{hi}\) | highest boiler firing | W |
Method and standards
Definitions of burner load and turndown; equal sharing between burners in service.
Where it is used
- Burner management settings.
- Choosing burner number and size.
- Low-load operation planning.
Common mistakes
- Quoting turndown on a different basis (flow instead of heat).
- Assuming equal sharing when burners are not balanced.
- Ignoring minimum load of the mills or fuel system.
Assumptions and limits
- Equal load on all burners in service.
- The boiler heat input and the burner ratings must be on the same calorific basis: burner makers often rate on net (NCV) input, while boiler input is often quoted on gross (GCV).
References
- Definitions of burner load and turndown
Questions and answers
How many burners should be in service?
Enough that each fires between its minimum and maximum. 80 MW with 4 of 6 burners rated 20 MW is 20 MW each, 100 % load; with these 4 burners the boiler can fire from 24 to 80 MW.
What is turndown?
Maximum over minimum stable firing of one burner: 20 MW over 6 MW is 3.3:1. The boiler's turndown with several burners is wider, by switching burners on and off.
Why not run all burners at low load?
Below the minimum stable rating flames become unstable and CO rises; the burner management system must keep each burner above it.
Method and article reviewed by FireCAD engineering on 11 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.