Burner Air Throat Velocity and Pressure Drop

Combustion air velocity in a burner throat and the air-side pressure drop by the orifice equation, from air flow, temperature, pressure and throat diameter.

Thermal power plantProcess steam and utilitiesSugar mill and cogenerationDistillery and ethanolRefinery and petrochemicalBurner and furnaceFan and blower

Inputs

Examples: 30 t/h hot airCold air burner

0.8 is a FireCAD starting value for a rounded throat; use the burner maker's figure. The pressure drop scales with 1/C_d².

Results

Hot air needs a larger throat for the same pressure drop; check at maximum and minimum firing.

Air density1.1837kg/m³
Throat velocity26.560m/s
Air-side pressure drop75.684mmWC

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 30 t/h hot air. The inputs, in the units selected above:

InputValue
Air flow to the burner30.000 t/h
Air temperature250.00 °C
Air pressure (absolute)104.00 kPa
Throat diameter550.00 mm
Discharge coefficient0.80000 -

Applying the formula below gives:

ResultValue
Air density0.69257 kg/m³
Throat velocity50.646 m/s
Air-side pressure drop141.52 mmWC

Open this example in the calculator and change any input.

Formula

\(\rho_a = \frac{p\,M_{da}}{R\,T_a}, \quad A = \frac{\pi d^2}{4}, \quad v = \frac{\dot m_a}{\rho_a A}, \quad \Delta p = \frac{1}{2\rho_a}\left(\frac{\dot m_a}{C_d A}\right)^2\)

Variables

Symbol Meaning SI unit
\(\dot m_a\) Air flow to the burner kg/s
\(T_a\) Air temperature K
\(p\) Air pressure (absolute) Pa
\(d\) Throat diameter m
\(C_d\) Discharge coefficient -
\(\rho_a\) Air density kg/m³
\(A\) throat area m²
\(M_{da}\) molar mass of dry air, 28.96 kg/kmol
\(R\) universal gas constant J/(kmol·K)
\(v\) Throat velocity m/s
\(\Delta p\) Air-side pressure drop Pa

Method and standards

Dry-air density by the ideal-gas law at the throat temperature and pressure, continuity for the velocity, and the orifice equation with a discharge coefficient for the pressure drop. The default \(C_d\) of 0.8 is a FireCAD starting value, not a published one; the drop scales with \(1/C_d^2\), so use the burner maker's figure.

Where it is used

  • Burner and FD fan sizing.
  • Burner troubleshooting.

Common mistakes

  • Using cold air density for preheated air.

Assumptions and limits

  • Incompressible flow.
  • Dry air: combustion air humidity (1–2 % by mass) lowers the density slightly, so the velocity is a little higher than shown.

References

  • Continuity and orifice equation Δp = (ṁ/(C_d A))²/(2ρ); dry-air molar mass (US Standard Atmosphere composition)

Questions and answers

Why does throat velocity matter?

It sets mixing and flame shape; too low and the flame lazes, too high and it lifts.

Windbox pressure?

The burner drop plus register losses; the FD fan must supply it.

mmWC?

Millimetres of water column, a common unit for burner pressure drops; 1 mmWC is about 9.81 Pa.

Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.