Worked example
Example: 30 t/h hot air. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Air flow to the burner | 30.000 t/h |
| Air temperature | 250.00 °C |
| Air pressure (absolute) | 104.00 kPa |
| Throat diameter | 550.00 mm |
| Discharge coefficient | 0.80000 - |
Applying the formula below gives:
| Result | Value |
|---|---|
| Air density | 0.69257 kg/m³ |
| Throat velocity | 50.646 m/s |
| Air-side pressure drop | 141.52 mmWC |
Open this example in the calculator and change any input.
Formula
\(\rho_a = \frac{p\,M_{da}}{R\,T_a}, \quad A = \frac{\pi d^2}{4}, \quad v = \frac{\dot m_a}{\rho_a A}, \quad \Delta p = \frac{1}{2\rho_a}\left(\frac{\dot m_a}{C_d A}\right)^2\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\dot m_a\) | Air flow to the burner | kg/s |
| \(T_a\) | Air temperature | K |
| \(p\) | Air pressure (absolute) | Pa |
| \(d\) | Throat diameter | m |
| \(C_d\) | Discharge coefficient | - |
| \(\rho_a\) | Air density | kg/m³ |
| \(A\) | throat area | m² |
| \(M_{da}\) | molar mass of dry air, 28.96 | kg/kmol |
| \(R\) | universal gas constant | J/(kmol·K) |
| \(v\) | Throat velocity | m/s |
| \(\Delta p\) | Air-side pressure drop | Pa |
Method and standards
Dry-air density by the ideal-gas law at the throat temperature and pressure, continuity for the velocity, and the orifice equation with a discharge coefficient for the pressure drop. The default \(C_d\) of 0.8 is a FireCAD starting value, not a published one; the drop scales with \(1/C_d^2\), so use the burner maker's figure.
Where it is used
- Burner and FD fan sizing.
- Burner troubleshooting.
Common mistakes
- Using cold air density for preheated air.
Assumptions and limits
- Incompressible flow.
- Dry air: combustion air humidity (1–2 % by mass) lowers the density slightly, so the velocity is a little higher than shown.
References
- Continuity and orifice equation Δp = (ṁ/(C_d A))²/(2ρ); dry-air molar mass (US Standard Atmosphere composition)
Questions and answers
Why does throat velocity matter?
It sets mixing and flame shape; too low and the flame lazes, too high and it lifts.
Windbox pressure?
The burner drop plus register losses; the FD fan must supply it.
mmWC?
Millimetres of water column, a common unit for burner pressure drops; 1 mmWC is about 9.81 Pa.
Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.