FireCADCalc

Lever Safety Valve Weight and Position

Weight to hang on a lever safety valve, or where to hang it, for a blow-off pressure, by moments about the fulcrum including the lever and valve weights.

Thermal power plantProcess steam and utilitiesSugar mill and cogenerationPulp and paperFood, dairy and textileBoilerBoiler attendant and boiler operator examinations

Inputs

Examples: 10 kg/cm² g, 80 mm valve, 100 mm / 800 mm, 10 kg lever7 kg/cm² g, 60 mm, 80 / 700 mm, 8 kg lever, 30 kg weight12 bar g, 50 mm, 75 / 900 mm, weightless lever

The diameter at which the disc seals on the seat; exam questions give it as the valve diameter. The force goes with its square.

Lever

Results

Moments about the fulcrum: F a = g (W L + m_l l_g + m_v a). Friction in the pins is ignored.

Steam force on the valve1,940.9N
Weight needed at distance L18.448kg
Distance for the weight available0.43045m

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 10 kg/cm² g, 80 mm valve, 100 mm / 800 mm, 10 kg lever. The inputs, in the units selected above:

InputValue
Blow-off pressure9.8066 bar g
Valve diameter (area the steam acts on)80.000 mm
Fulcrum to valve centre100.00 mm
Fulcrum to the weight0.80000 m
Mass of the lever10.000 kg
Fulcrum to the lever's centre of gravity0.45000 m
Mass of the valve and spindle2.0000 kg
Weight available (to find its position)50.000 kg

Applying the formula below gives:

ResultValue
Steam force on the valve4,929.4 N
Weight needed at distance L56.957 kg
Distance for the weight available0.91131 m

Open this example in the calculator and change any input.

Formula

\(F = (p - p_{atm})\, \frac{\pi d^2}{4}\)

\(F\, a = g\,(W L + m_l\, l_g + m_v\, a)\)

Variables

Symbol Meaning SI unit
\(p\) Blow-off pressure Pa
\(d\) Valve diameter where the disc seals on the seat (area the steam acts on) m
\(a\) Fulcrum to valve centre m
\(L\) Fulcrum to the weight m
\(m_l\) Mass of the lever kg
\(l_g\) Fulcrum to the lever's centre of gravity m
\(m_v\) Mass of the valve and spindle kg
\(m_w\) Weight available (to find its position) kg
\(F\) Steam force on the valve N
\(W\) Weight needed at distance L kg
\(L_W\) Distance for the weight available m

Method and standards

Moments about the fulcrum at the instant the valve lifts: the steam force at distance a balances the weight, the lever's own weight and the valve's weight.

Worked example

A lever safety valve of 80 mm diameter is 100 mm from the fulcrum. The lever weighs 10 kg with its centre 450 mm from the fulcrum, and the valve weighs 2 kg. What weight at 800 mm makes it blow at 10 kg/cm² g?

  • Steam force = 10 × 98 066.5 Pa × π × 0.08²/4 = 4929 N
  • Moment of steam = 4929 × 0.1 = 492.9 N·m, which is 50.26 kg·m
  • Less lever 10 × 0.45 = 4.5 kg·m and valve 2 × 0.1 = 0.2 kg·m leaves 45.56 kg·m
  • Weight = 45.56 / 0.8 = 57.0 kg

Where it is used

  • Boiler attendant examinations (lever valves on old Lancashire and Cornish boilers).
  • Checking an old lever-type valve's setting.
  • Teaching moments in statics.

Common mistakes

  • Using absolute pressure.
  • Leaving out the lever's own weight.
  • Measuring distances from the valve instead of the fulcrum.

Assumptions and limits

  • Static balance; spindle friction neglected.
  • The steam acts on the area at the seat sealing diameter; the force goes with its square, so use that diameter, not the inlet pipe bore.
  • Atmospheric pressure is taken as the standard 101.325 kPa. Enter the blow-off pressure as gauge; an absolute pressure measured at altitude would overstate the gauge pressure by the drop in atmospheric pressure.
  • Modern boilers use spring-loaded valves to code; this is a principle calculation.

References

  • Moments about a fulcrum (statics, textbook)

Questions and answers

What weight does an 80 mm valve need at 800 mm to blow at 10 kg/cm² g?

The steam pushes with 4929 N, 100 mm from the fulcrum. Less the 10 kg lever (centre 450 mm) and 2 kg valve, a weight of 57.0 kg at 800 mm holds it.

Where would a 50 kg weight go?

At 911 mm from the fulcrum, beyond the 800 mm lever: a longer lever or a heavier weight is needed.

Why gauge pressure?

Atmospheric pressure acts on the outside of the valve too, so only the gauge pressure lifts it.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.