Worked example
Example: Coal to bagasse. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Fuel A rate | 4.0000 t/h |
| Fuel A GCV | 23,000 kJ/kg |
| Efficiency on fuel A (on GCV) | 82.000 % |
| Fuel B GCV | 9,600.0 kJ/kg |
| Efficiency on fuel B (on GCV) | 70.000 % |
Applying the formula below gives:
| Result | Value |
|---|---|
| Fuel B rate | 11.226 t/h |
| Tonnes of B per tonne of A | 2.8065 |
Open this example in the calculator and change any input.
Formula
\(\frac{\dot m_B}{\dot m_A} = \frac{GCV_A \eta_A}{GCV_B \eta_B}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\dot m_A\) | Fuel A rate | kg/s |
| \(GCV_A\) | Fuel A GCV | J/kg |
| \(\eta_A\) | Efficiency on fuel A | - |
| \(GCV_B\) | Fuel B GCV | J/kg |
| \(\eta_B\) | Efficiency on fuel B | - |
| \(\dot m_B\) | Fuel B rate | kg/s |
| \(\dot m_B/\dot m_A\) | Tonnes of B per tonne of A | - |
Method and standards
Useful heat balance: the same steam output needs the same useful heat, \(\dot m_B\,GCV_B\,\eta_B = \dot m_A\,GCV_A\,\eta_A\).
Where it is used
- Fuel switching studies.
- Off-season fuel planning.
Common mistakes
- Ignoring the efficiency difference.
Assumptions and limits
- Same steam output.
- Calorific values and efficiencies must share one basis: gross values with efficiencies on GCV (as labelled), or net values with net efficiencies. Mixing a GCV with a net efficiency gives a wrong ratio and cannot be detected.
References
- Useful heat balance between two fuels (definition)
Questions and answers
Why include efficiency?
Wet fuels lose more heat in the stack, so more fuel is needed than the calorific values alone suggest.
Same basis?
Both GCVs with gross efficiencies, or both NCVs with net.
Handling?
Two or three times the tonnage of biomass needs bigger feeders and storage.
Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.