FireCADCalc

Boiler Efficiency Quick Formula (Gas or Oil)

Boiler or heater efficiency on HHV and LHV basis from excess air and the exit-gas-to-ambient temperature difference for natural gas or fuel oil (Ganapathy Eq. 16).

Thermal power plantProcess steam and utilitiesSugar mill and cogenerationChemical and fertiliserPulp and paperFood, dairy and textileBoiler

Inputs

Examples: Ganapathy: gas, 15 %, 280/80 °FOil, 20 %, 400/80 °F

Results

The expressions include 1 % for radiation and unaccounted losses and assume complete combustion.

Efficiency, HHV basis85.169%
Efficiency, LHV basis90.762%

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Ganapathy: gas, 15 %, 280/80 °F. The inputs, in the units selected above:

InputValue
FuelNatural gas
Excess air15.000 %
Exit gas temperature137.78 °C
Ambient temperature26.667 °C

Applying the formula below gives:

ResultValue
Efficiency, HHV basis84.690 %
Efficiency, LHV basis93.783 %

Open this example in the calculator and change any input.

Formula

Natural gas:

\(\eta_{HHV} = 89.4 - (0.001123 + 0.0195\,f)\,\Delta T, \quad \eta_{LHV} = 99.0 - (0.001244 + 0.0216\,f)\,\Delta T\)

Fuel oil:

\(\eta_{HHV} = 92.9 - (0.001298 + 0.01905\,f)\,\Delta T, \quad \eta_{LHV} = 99.0 - (0.001383 + 0.0203\,f)\,\Delta T\)

\(f = 1 + EA, \quad \Delta T = 1.8\,(t_g - t_a) \text{ in °F}, \quad \eta \text{ in per cent}\)

Variables

Symbol Meaning SI unit
\(\text{fuel}\) Fuel -
\(EA\) Excess air, fraction (15 % = 0.15) -
\(f\) excess air factor, \(1 + EA\) -
\(\Delta T\) exit gas minus ambient temperature, in °F °F
\(t_g\) Exit gas temperature K
\(t_a\) Ambient temperature K
\(\eta_{HHV}\) Efficiency, HHV basis -
\(\eta_{LHV}\) Efficiency, LHV basis -

Method and standards

Ganapathy's Eqs. (16a–b), derived from combustion calculations for typical gas and oil; the HHV and LHV forms are both from the same source.

Where it is used

  • Operator checks of package boilers.
  • Excess air tuning.

Common mistakes

  • Using for coal or biomass.
  • Entering ΔT in kelvin into the °F formula (the calculator converts).

Assumptions and limits

  • Natural gas or fuel oil; 1 % other losses.
  • A warning appears above 60 % excess air or 300 K gas-to-ambient difference, where the linear fit is extrapolated.

References

  • Ganapathy
  • Steam Plant Calculations Manual
  • 2nd ed. (Marcel Dekker, 1993)
  • Q2.22
  • Eqs. (16a) and (16b)

Questions and answers

How good is it?

Within about half a point for typical natural gas and oil firing.

What is EA here?

You enter the excess air (15 %); the formula uses the excess air factor f = 1 + EA, so 15 % excess air is 1.15.

What does Ganapathy's example give?

Natural gas, 15 % excess air, 280 °F stack and 80 °F ambient: 84.6 % HHV, 93.8 % LHV.

Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.