FireCADCalc

Film Condensation on Horizontal Tubes (Nusselt)

Condensing coefficient of steam on a horizontal tube and a vertical row of N tubes by Nusselt's film theory, with IF97 liquid properties.

Thermal power plantProcess steam and utilitiesSugar mill and cogenerationDistillery and ethanolChemical and fertiliserIAPWS-IF97 (water and steam)Condenser and cooling tower

Inputs

Examples: 2 bar steam, 25 mm tubesVacuum condenser

Results

Liquid properties at saturation; non-condensable gas sharply lowers the coefficient. Kern's N^−1/6 is a less conservative row correction.

Coefficient, single tube13,168W/(m²·K)
Mean coefficient, row of N tubes (N^−1/4)6,226.8W/(m²·K)
Heat flux, single tube65.840kW/m²

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 2 bar steam, 25 mm tubes. The inputs, in the units selected above:

InputValue
Steam pressure (absolute)2.0000 bar
T_sat − T_wall8.0000 K
Tube outside diameter25.000 mm
Tubes in a vertical row10.000 -

Applying the formula below gives:

ResultValue
Coefficient, single tube13,917 W/(m²·K)
Mean coefficient, row of N tubes (N^−1/4)7,826.4 W/(m²·K)
Heat flux, single tube111.34 kW/m²

Open this example in the calculator and change any input.

Formula

\(h_1 = 0.729\left[\frac{g\rho_l(\rho_l - \rho_v)h'_{fg}k_l^3}{\mu_l \Delta T D}\right]^{1/4}, \quad h_N = h_1 N^{-1/4}\)

Variables

Symbol Meaning SI unit
\(p\) Steam pressure (absolute) Pa
\(\Delta T\) T_sat − T_wall K
\(D\) Tube outside diameter m
\(N\) Tubes in a vertical row -
\(h_1\) Coefficient, single tube W/(m²·K)
\(h_N\) Mean coefficient, row of N tubes (N^−1/4) W/(m²·K)
\(q\) Heat flux, single tube W/m²

Method and standards

Nusselt.

Where it is used

  • Condensers, juice heaters and steam heaters.
  • Teaching condensation.

Common mistakes

  • ΔT taken as steam minus cooling water.

Assumptions and limits

  • Laminar film, pure vapour.
  • Liquid properties at saturation. Incropera (and the vertical-surface calculator here) take them at the film temperature (T_sat + T_wall)/2; for large ΔT the two differ by a few per cent.

References

  • Nusselt film theory for a horizontal cylinder
  • h = 0.729 [g ρ_l(ρ_l − ρ_v) h′_fg k³/(μ ΔT D)]^¼
  • h′_fg = h_fg + 0.68 c_p ΔT
  • row of N tubes × N^−¼ (Incropera); properties from IAPWS-IF97

Questions and answers

Why does the coefficient fall down a tube row?

Condensate from upper tubes thickens the film on lower ones.

Why add 0.68 c_p ΔT?

It accounts for sub-cooling of the condensate film (Rohsenow's modification).

Air in the steam?

Even a small amount of air blankets the tubes and cuts the coefficient a lot.

Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.