Generator Synchronising: Slip, Advance Angle and Breaker Voltage

Slip frequency, beat period and synchroscope speed when paralleling a generator, the breaker closing advance angle and the voltage across the open breaker.

Inputs

Examples: Illustrative 11 kV generatorSlow incoming 415 V set60 Hz 13.8 kV unit

Accepted: 1 to 1,000 Hz
Accepted: 1 to 1,000 Hz
Accepted: 1 to 1,000,000 V
Accepted: 1 to 1,000,000 V
Accepted: -180 to 180 °
Accepted: 1 to 2,000 ms

Results

The phase angle between the incoming machine and the bus advances by 360° every 1/Δf seconds (the synchroscope turns at Δf revolutions per second, clockwise when the generator is fast). Because the breaker takes t_cb to close, the close command must be given an angle 360°·Δf·t_cb before coincidence. The voltage across the open breaker is |V_g − V_b∠δ|, reaching V_g + V_b at 180°. Typical limits for automatic synchronisers are about 0.1–0.2 Hz slip, ±10° and ±5 % voltage, with the generator slightly fast so it picks up load on closing.

Slip frequency-0.10000Hz
Beat (slip) period10.0000s
Advance angle to cover the breaker closing time1.8000°
Voltage across the open breaker at δ178.63V
Maximum voltage across the breaker (out of phase)825.00V
Voltage mismatch-1.2048%

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Illustrative 11 kV generator. The inputs, in the units selected above:

InputValue
Incoming generator frequency50.120 Hz
Bus frequency50.000 Hz
Incoming generator voltage11,100 V
Bus voltage11,000 V
Present phase angle between them10.000 °
Breaker closing time80.000 ms

Applying the formula below gives:

ResultValue
Slip frequency0.12000 Hz
Beat (slip) period8.3333 s
Advance angle to cover the breaker closing time3.4560 °
Voltage across the open breaker at δ1,928.7 V
Maximum voltage across the breaker (out of phase)22,100 V
Voltage mismatch0.90909 %

Open this example in the calculator and change any input.

Formula

\(\Delta f = f_g - f_b, \quad \delta_{adv} = 360°\,\Delta f\,t_{cb}, \quad V_{CB} = \sqrt{V_g^2 + V_b^2 - 2V_gV_b\cos\delta}\)

Variables

Symbol Meaning SI unit
\(f_g\) Incoming generator frequency 1/s
\(f_b\) Bus frequency 1/s
\(V_g\) Incoming generator voltage V
\(V_b\) Bus voltage V
\(\delta\) Present phase angle between them rad
\(t_{cb}\) Breaker closing time s
\(\Delta f\) Slip frequency 1/s
\(T_s\) Beat (slip) period s
\(\delta_{adv}\) Advance angle to cover the breaker closing time rad
\(V_{CB}\) Voltage across the open breaker at δ V
\(V_{CB,max}\) Maximum voltage across the breaker (out of phase) V
\(\Delta V\) Voltage mismatch -

Method and standards

Synchronising.

Where it is used

  • Setting up synchronisers and check-synchronising relays.
  • Training on manual synchronising.

Common mistakes

  • Ignoring the breaker closing time.
  • Closing with the generator slow (reverse power).

Assumptions and limits

  • Steady slip during the closing time; balanced three-phase voltages.

References

  • Synchronising of synchronous machines

Questions and answers

Why should the generator run slightly fast?

So that on closing it takes up a little load rather than motoring.

What happens if the breaker closes far out of phase?

Large circulating current and torque transients that can damage the shaft and couplings.

What do the defaults represent?

An illustrative 11 kV generator at 50.12 Hz and 11.1 kV synchronising to a 50 Hz, 11 kV bus, now 10° apart, with an 80 ms breaker.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Sources

Kundur, Power System Stability and Control (McGraw-Hill, 1994)

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.