Average Power Factor from kWh and kvarh Readings

Average power factor over a billing period from the kWh and kvarh consumed (or kWh and kVAh), with the kVAh, tan φ and the phase angle.

Thermal power plantProcess steam and utilities

Inputs

Examples: 120 000 kWh and 60 000 kvarh45 000 kWh and 15 000 kvarh8 000 kWh, no kvarh

Results

Average power factor0.89443
Apparent energy (kVAh)134,164
tan φ (kvarh / kWh)0.50000
Average phase angle26.565°

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 120 000 kWh and 60 000 kvarh. The inputs, in the units selected above:

InputValue
Active energy in the period (kWh)120,000 -
Reactive energy in the period (kvarh)60,000 -

Applying the formula below gives:

ResultValue
Average power factor0.89443
Apparent energy (kVAh)134,164
tan φ (kvarh / kWh)0.50000
Average phase angle26.565 °

Open this example in the calculator and change any input.

Formula

\(\cos\varphi = \frac{E_P}{\sqrt{E_P^2 + E_Q^2}}, \quad E_S = \sqrt{E_P^2 + E_Q^2}\)

Variables

Symbol Meaning SI unit
\(E_P\) Active energy in the period (kWh) -
\(E_Q\) Reactive energy in the period (kvarh) -
\(\cos\varphi\) Average power factor -
\(E_S\) Apparent energy (kVAh) -
\(\tan\varphi\) tan φ (kvarh / kWh) -
\(\varphi\) Average phase angle rad

Method and standards

Power triangle with energies over the period.

Where it is used

  • Checking electricity bills.
  • Sizing correction from monthly data.

Common mistakes

  • Adding lag and lead kvarh.
  • Using kVA demand instead of kVAh.

Assumptions and limits

  • Lagging kvarh only; harmonics ignored.
  • kVAh is the vector sum of the period energies; an integrating kVAh meter reads higher when the load varies.

References

  • Power triangle applied to energies

Questions and answers

What is the power factor for 120 000 kWh and 60 000 kvarh?

0.894; kVAh = 134164.

Is this what the utility bills on?

Many tariffs use this average (kWh/kVAh); check whether yours counts leading kvarh.

Why can it differ from the instantaneous reading?

It is energy-weighted over the whole period. A kVAh meter that integrates apparent power over time reads at least the vector sum √(kWh² + kvarh²) used here, and more when the load varies, so a billing power factor on kWh/kVAh can be lower than this.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.