FireCADCalc

Corona: Critical Disruptive Voltage (Peek)

Critical disruptive voltage for corona on an overhead line from conductor radius, phase spacing, air density and surface factor (Peek's formula).

Thermal power plantProcess steam and utilitiesSugar mill and cogenerationChemical and fertiliserPulp and paperFood, dairy and textile

Inputs

Examples: 25 mm conductor at 5 m, 220 kVAt 1,500 m altitude

Results

Peek's formula with g₀ = 21.1 kV rms/cm (30 kV peak/cm) at 25 °C and 1 atm. Rain and fog lower V_c by about 20 %; visual corona starts somewhat above V_c.

Air density factor1.0000
Critical disruptive line voltage232.65kV
Operating to critical voltage0.94562

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 25 mm conductor at 5 m, 220 kV. The inputs, in the units selected above:

InputValue
Conductor radius12.500 mm
Phase spacing (or GMD)5.0000 m
Surface irregularity factor0.85000 -
Air pressure101.33 kPa
Air temperature25.000 °C
Operating line voltage220.00 kV

Applying the formula below gives:

ResultValue
Air density factor1.0000
Critical disruptive line voltage232.65 kV
Operating to critical voltage0.94562

Open this example in the calculator and change any input.

Formula

\(V_{c,ph} = g_0m_0\delta r\ln\frac Dr, \quad g_0 = 21.1\ \mathrm{kV_{rms}/cm}, \quad \delta = \frac{p}{p_0}\frac{T_0}{T}\)

Variables

Symbol Meaning SI unit
\(r\) Conductor radius m
\(D\) Phase spacing (or GMD) m
\(m_0\) Surface irregularity factor -
\(p\) Air pressure Pa
\(T\) Air temperature K
\(V\) Operating line voltage V
\(\delta\) Air density factor -
\(V_c\) Critical disruptive line voltage V
\(V/V_c\) Operating to critical voltage -

Method and standards

Peek's formula.

Where it is used

  • Line conductor selection.
  • Explaining hum and radio interference.

Common mistakes

  • Radius in metres where the formula uses cm (the calculator converts).
  • Ignoring weather.

Assumptions and limits

  • Smooth, fair-weather conditions with m₀.
  • Single conductor per phase: bundled conductors (two or more sub-conductors) need the equivalent radius and are not covered by the inputs.
  • Reference conditions p₀ = 101 325 Pa and T₀ = 298.15 K (25 °C) for δ; V_c,ph in kV rms with r in cm, multiplied by √3 for the line voltage.

References

  • Peek's critical disruptive voltage (V_c = g₀m₀δr ln(D/r))
  • as in Stevenson and Kothari–Nagrath

Questions and answers

Why do high-voltage lines use bundled conductors?

A bundle acts like a larger radius, lowering the surface gradient and pushing V_c above the operating voltage.

Why does altitude matter?

Thinner air (lower δ) breaks down at a lower gradient; lines at altitude need larger conductors.

What do the defaults represent?

A 25 mm conductor at 5 m spacing at 220 kV in standard air.

Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.