Worked example
Example: 25 mm conductor at 5 m, 220 kV. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Conductor radius | 12.500 mm |
| Phase spacing (or GMD) | 5.0000 m |
| Surface irregularity factor | 0.85000 - |
| Air pressure | 101.33 kPa |
| Air temperature | 25.000 °C |
| Operating line voltage | 220.00 kV |
Applying the formula below gives:
| Result | Value |
|---|---|
| Air density factor | 1.0000 |
| Critical disruptive line voltage | 232.65 kV |
| Operating to critical voltage | 0.94562 |
Open this example in the calculator and change any input.
Formula
\(V_{c,ph} = g_0m_0\delta r\ln\frac Dr, \quad g_0 = 21.1\ \mathrm{kV_{rms}/cm}, \quad \delta = \frac{p}{p_0}\frac{T_0}{T}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(r\) | Conductor radius | m |
| \(D\) | Phase spacing (or GMD) | m |
| \(m_0\) | Surface irregularity factor | - |
| \(p\) | Air pressure | Pa |
| \(T\) | Air temperature | K |
| \(V\) | Operating line voltage | V |
| \(\delta\) | Air density factor | - |
| \(V_c\) | Critical disruptive line voltage | V |
| \(V/V_c\) | Operating to critical voltage | - |
Method and standards
Peek's formula.
Where it is used
- Line conductor selection.
- Explaining hum and radio interference.
Common mistakes
- Radius in metres where the formula uses cm (the calculator converts).
- Ignoring weather.
Assumptions and limits
- Smooth, fair-weather conditions with m₀.
- Single conductor per phase: bundled conductors (two or more sub-conductors) need the equivalent radius and are not covered by the inputs.
- Reference conditions p₀ = 101 325 Pa and T₀ = 298.15 K (25 °C) for δ; V_c,ph in kV rms with r in cm, multiplied by √3 for the line voltage.
References
- Peek's critical disruptive voltage (V_c = g₀m₀δr ln(D/r))
- as in Stevenson and Kothari–Nagrath
Questions and answers
Why do high-voltage lines use bundled conductors?
A bundle acts like a larger radius, lowering the surface gradient and pushing V_c above the operating voltage.
Why does altitude matter?
Thinner air (lower δ) breaks down at a lower gradient; lines at altitude need larger conductors.
What do the defaults represent?
A 25 mm conductor at 5 m spacing at 220 kV in standard air.
Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.