Worked example
Example: 4 poles, 1 500 rpm, 30 mWb, 40 turns. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Number of poles | 4.0000 - |
| Speed | 1,500.0 rpm |
| Flux per pole | 30.000 mWb |
| Turns in series per phase | 40.000 - |
| Pitch factor | 0.96600 - |
| Distribution factor | 0.96000 - |
Applying the formula below gives:
| Result | Value |
|---|---|
| Frequency P N / 2 | 50.000 Hz |
| EMF per phase | 247.21 V |
| Line voltage, star connected | 428.18 V |
| Winding factor k_p k_d | 0.92736 |
Open this example in the calculator and change any input.
Formula
\(f = \frac{P N}{2}, \quad E_{ph} = \sqrt 2\, \pi\, k_p k_d f \Phi T_{ph} \approx 4.44\, k_p k_d f \Phi T_{ph}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(P\) | Number of poles | - |
| \(N\) | Speed | 1/s |
| \(\Phi\) | Flux per pole | Wb |
| \(T_{ph}\) | Turns in series per phase | - |
| \(k_p\) | Pitch factor | - |
| \(k_d\) | Distribution factor | - |
| \(f\) | Frequency P N / 2 | 1/s |
| \(E_{ph}\) | EMF per phase | V |
| \(E_L\) | Line voltage, star connected | V |
| \(k_w\) | Winding factor k_p k_d | - |
Method and standards
RMS EMF of a distributed, short-pitched winding.
Where it is used
- Electrical examinations.
- Generator rewinding checks.
Common mistakes
- Using conductors as turns.
- Speed in rpm in f = PN/2.
Assumptions and limits
- Sinusoidal flux distribution.
- The number of poles must be an even whole number.
References
- Synchronous machine EMF equation E_ph = √2 π k_p k_d f Φ T_ph (textbook)
Questions and answers
What EMF for 4 poles, 1500 rpm, 30 mWb, 40 turns, k_p 0.966, k_d 0.96?
50 Hz; 247.2 V per phase, 428.2 V line.
Turns or conductors?
Turns per phase T = Z/2, where Z is the conductors in series per phase.
Why short-pitch the coils?
It lowers the EMF a little but removes harmonics.
Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.