Worked example
Example: 25 mm conductor, flat 4–4–8 m. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Conductor radius | 12.500 mm |
| Spacing phase 1–2 | 4.0000 m |
| Spacing phase 2–3 | 4.0000 m |
| Spacing phase 3–1 | 8.0000 m |
| Frequency | 50.000 Hz |
Applying the formula below gives:
| Result | Value |
|---|---|
| Geometric mean distance | 5.0397 m |
| Inductance per length | 1.2499 mH/km |
| Reactance (Ω/km) | 0.39266 |
| Capacitance to neutral per length | 9.2731 nF/km |
| Susceptance (µS/km) | 2.9132 |
Open this example in the calculator and change any input.
Formula
\(GMD = \sqrt[3]{D_{12}D_{23}D_{31}}, \quad L' = 2\times10^{-7}\ln\frac{GMD}{0.7788r}, \quad C' = \frac{2\pi\varepsilon_0}{\ln(GMD/r)}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(r\) | Conductor radius | m |
| \(D_{12}\) | Spacing phase 1–2 | m |
| \(D_{23}\) | Spacing phase 2–3 | m |
| \(D_{31}\) | Spacing phase 3–1 | m |
| \(f\) | Frequency | 1/s |
| \(GMD\) | Geometric mean distance | m |
| \(L'\) | Inductance (mH/km) | - |
| \(X'\) | Reactance (Ω/km) | - |
| \(C'\) | Capacitance to neutral (nF/km) | - |
| \(B'\) | Susceptance (µS/km) | - |
Method and standards
Line constants.
Where it is used
- Plant overhead lines.
- Fault and load-flow data.
Common mistakes
- Using diameter for radius.
- Ignoring bundle GMR.
Assumptions and limits
- Transposed; solid conductors. There is no GMR input: for stranded (ACSR) or bundled conductors the maker's GMR differs from 0.7788r, so the inductance here is approximate.
- L′ = 2 × 10⁻⁷ ln(GMD/GMR) H/m uses the classical μ₀/2π = 2 × 10⁻⁷. Results are shown in mH/km, Ω/km, nF/km and µS/km in every unit system.
References
- Stevenson and Grainger
- Power System Analysis (McGraw-Hill, 1994); Kothari and Nagrath
- Modern Power System Analysis
- 4th ed. (2011) (L = 2×10⁻⁷ ln(GMD/GMR) H/m, C = 2πε₀/ln(GMD/r) F/m)
Questions and answers
Why does wider spacing raise inductance?
More flux links the loop between conductors; inductance grows with the log of spacing.
What is GMR?
The radius of an equivalent thin-walled conductor with the same internal plus external flux: 0.7788r for a solid round wire.
What do the defaults represent?
A 25 mm diameter conductor in a flat 4–4–8 m configuration at 50 Hz.
Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.