Worked example
Example: 1 000 kW connected, 600 kW demand, 259 200 kWh in 720 h. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Connected load | 1,000.0 kW |
| Maximum demand of the installation | 600.00 kW |
| Energy used in the period | 259,200 kWh |
| Length of the period | 720.00 h |
| Sum of the individual maximum demands | 750.00 kW |
Applying the formula below gives:
| Result | Value |
|---|---|
| Demand factor (maximum demand / connected load) | 60.000 % |
| Average load | 360.00 kW |
| Load factor (average / maximum demand) | 60.000 % |
| Diversity factor (sum of individual maxima / maximum demand) | 1.2500 |
| Coincidence factor (1 / diversity factor) | 0.80000 |
Open this example in the calculator and change any input.
Formula
\(DF = \frac{P_{md}}{P_c}, \quad LF = \frac{E / t}{P_{md}}, \quad F_d = \frac{\Sigma P_i}{P_{md}}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(P_c\) | Connected load | W |
| \(P_{md}\) | Maximum demand of the installation | W |
| \(E\) | Energy used in the period | J |
| \(t\) | Length of the period | s |
| \(\Sigma P_i\) | Sum of the individual maximum demands | W |
| \(DF\) | Demand factor (maximum demand / connected load) | - |
| \(P_{avg}\) | Average load | W |
| \(LF\) | Load factor (average / maximum demand) | - |
| \(F_d\) | Diversity factor (sum of individual maxima / maximum demand) | - |
| \(F_c\) | Coincidence factor (1 / diversity factor) | - |
Method and standards
Definitions.
Where it is used
- Transformer and feeder sizing.
- Tariff analysis.
- Electrical examinations.
Common mistakes
- Mixing kW and kVA.
- Inverting the diversity factor.
Assumptions and limits
- One period; kW values. A load factor above 1 is flagged as inconsistent data.
References
- Definitions of demand
- load and diversity factors (IEC 60050-691 terminology)
Questions and answers
What are the factors for 1000 kW connected, 600 kW maximum demand and 259 200 kWh in 720 h?
Demand factor 0.60, average load 360 kW, load factor 0.60.
Is diversity factor above or below 1?
By the IEC definition used here, 1 or more. Some texts use its inverse, the coincidence factor.
Why does load factor matter?
A higher load factor spreads the demand charge over more kWh.
Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.