Worked example
Example: Plant 500 kW, 0.75 to 0.95, 415 V. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Active power of the load | 500.00 kW |
| Present power factor | 0.75000 - |
| Target power factor | 0.95000 - |
| Line-to-line voltage (three-phase) | 415.00 V |
Applying the formula below gives:
| Result | Value |
|---|---|
| Capacitor rating required | 276.62 kvar |
| Reactive power before | 440.96 kvar |
| Reactive power after | 164.34 kvar |
| Apparent power before | 666.67 kVA |
| Apparent power after | 526.32 kVA |
| Line current before | 927.47 A |
| Line current after | 732.21 A |
| Reduction of line losses (I² R) | 37.673 % |
Open this example in the calculator and change any input.
Formula
\(Q_c = P\,(\tan\varphi_1 - \tan\varphi_2) \qquad Q_1 = P\tan\varphi_1 \qquad Q_2 = P\tan\varphi_2\)
\(S_1 = \frac{P}{\cos\varphi_1} \qquad S_2 = \frac{P}{\cos\varphi_2} \qquad I = \frac{S}{\sqrt 3\,U} \qquad \Delta P_{loss} = 1 - \left(\frac{\cos\varphi_1}{\cos\varphi_2}\right)^2\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(P\) | active power of the load | W |
| \(\cos\varphi_1\) | present power factor | – |
| \(\cos\varphi_2\) | target power factor | – |
| \(U\) | line-to-line voltage | V |
| \(Q_c\) | capacitor rating required | var |
| \(Q_1\) | reactive power before | var |
| \(Q_2\) | reactive power after | var |
| \(S_1\) | apparent power before | VA |
| \(S_2\) | apparent power after | VA |
| \(I_1\) | line current before | A |
| \(I_2\) | line current after | A |
| \(\Delta P_{loss}\) | relative reduction of the I²R losses upstream | – |
Method and standards
The power triangle for a balanced three-phase load: active power is unchanged, the capacitor supplies the difference in reactive power. Capacitor ratings and duty are covered by IEC 60831-1.
Where it is used
- Sizing capacitor banks for plants and motors.
- Reducing demand charges and cable losses.
- Checking an existing bank after load changes.
Common mistakes
- Overcorrecting at light load.
- Ignoring harmonics from variable speed drives.
- Correcting a motor beyond its no-load magnetising current.
Assumptions and limits
- Sinusoidal voltage and current; harmonics need detuned banks and a separate study.
- Capacitor output is rated at its rated voltage; at a lower voltage it delivers (U/U_r)² of its rating.
- Losses are those upstream of the capacitor; the capacitor itself has small losses not included.
References
- IEC 60831-1 (shunt power capacitors, context); power triangle definitions
Questions and answers
How many kvar do I need to correct the power factor?
Q_c = P·(tanφ₁ − tanφ₂). A 500 kW load at 0.75 needs 277 kvar to reach 0.95; its current at 415 V falls from 927 A to 732 A.
How much do losses fall?
Line losses go with the square of the current, so they fall by 1 − (cosφ₁/cosφ₂)². From 0.75 to 0.95 that is 38 % of the losses upstream of the capacitor.
Why not correct to 1.0?
At light load a fixed bank sized for unity over-corrects and raises the voltage, and a bank near resonance amplifies harmonics. Most designs aim at 0.95–0.98 with automatic (APFC) steps and detuning reactors where harmonics exist.
Method and article reviewed by FireCAD engineering on 10 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.