Worked example
Example: 400 kW at 0.85, 10 % margin, 80 % loading. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Running load | 400.00 kW |
| Power factor of the load | 0.85000 - |
| Margin for growth | 10.000 % |
| Planned loading of the set | 80.000 % |
| Rated power factor of the generator | 0.80000 - |
| Voltage (three phase, line to line) | 415.00 V |
Applying the formula below gives:
| Result | Value |
|---|---|
| Load in kVA | 470.59 kVA |
| Generator rating needed | 687.50 kVA |
| kW rating at the generator's power factor | 550.00 kW |
| Full-load current of that rating | 956.45 A |
Open this example in the calculator and change any input.
Formula
\(S_L = \frac{P}{\cos\varphi}, \quad S_g = \max\left(\frac{S_L (1 + m)}{k_L},\ \frac{P (1 + m)}{k_L \cos\varphi_g}\right)\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(P\) | Running load | W |
| \(\cos\varphi\) | Power factor of the load | - |
| \(m\) | Margin for growth | - |
| \(k_L\) | Planned loading of the set | - |
| \(\cos\varphi_g\) | Rated power factor of the generator | - |
| \(V\) | Voltage (three phase, line to line) | V |
| \(S_L\) | Load in kVA | VA |
| \(S_g\) | Generator rating needed | VA |
| \(P_g\) | kW rating at the generator's power factor | W |
| \(I_g\) | Full-load current of that rating | A |
Method and standards
Alternator kVA and engine kW limits.
Where it is used
- Standby and prime power selection.
- Checking an existing set against added load.
Common mistakes
- Sizing on kW alone.
- Ignoring starting kVA.
Assumptions and limits
- Steady load; no step-load or harmonic derating.
- No site derating for altitude or ambient temperature (apply the maker's factors) and no motor-starting kVA check.
References
- S = P / cos φ; rating by kVA and by engine kW
Questions and answers
What generator for 400 kW at 0.85 power factor, 10 % margin, 80 % loading?
Load 471 kVA; by kW the engine needs 688 kVA at 0.8, which governs.
Why two checks?
The alternator limits kVA; the engine limits kW.
What about motor starting?
A large DOL motor can need several times its running kVA; ask the maker.