Worked example
Example: 75 kW at 415 V, 0.85, three phase. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Power (output, or input if efficiency is 100 %) | 75.000 kW |
| Voltage (line to line for three phase) | 415.00 V |
| Power factor (AC) | 0.85000 - |
| Efficiency | 100.00 % |
| Supply | Three phase AC |
Applying the formula below gives:
| Result | Value |
|---|---|
| Current | 122.75 A |
| Input power | 75.000 kW |
| Apparent power | 88.235 kVA |
| Reactive power | 46.481 kvar |
Open this example in the calculator and change any input.
Formula
\(I = \frac{P}{\sqrt 3\, V \cos\varphi\, \eta}\ (3\phi), \quad I = \frac{P}{V \cos\varphi\, \eta}\ (1\phi), \quad I = \frac{P}{V \eta}\ (\text{DC})\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(P\) | Power (output, or input if efficiency is 100 %) | W |
| \(V\) | Voltage (line to line for three phase) | V |
| \(\cos\varphi\) | Power factor (AC) | - |
| \(\eta\) | Efficiency | - |
| \(\text{supply}\) | Supply | - |
| \(I\) | Current | A |
| \(P_{in}\) | Input power | W |
| \(S\) | Apparent power | VA |
| \(Q\) | Reactive power | var |
Method and standards
Definition of active power.
Where it is used
- Feeder and breaker sizing.
- Checking a nameplate current.
Common mistakes
- Leaving out power factor.
- Using 230 V with the three-phase formula.
Assumptions and limits
- Balanced load, sinusoidal supply.
References
- AC power relations P = √3 V I cos φ (3φ)
- P = V I cos φ (1φ)
- P = V I (DC)
Questions and answers
How many amps does 75 kW take at 415 V, 0.85 power factor?
122.8 A.
Why include efficiency?
A motor's kW is shaft output; the supply delivers output ÷ efficiency.
And for DC?
I = P / V; there is no power factor.
Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.