Worked example
Example: HT meter 200/5 A, 11 kV/110 V, 1 500 kWh read. The inputs, in the units selected above:
| Input | Value |
|---|---|
| CT primary current | 200.00 A |
| CT secondary current | 5.0000 A |
| PT primary voltage (equal to secondary if no PT) | 11,000 V |
| PT secondary voltage | 110.00 V |
| CT ratio programmed in the meter (1 = none) | 1.0000 - |
| PT ratio programmed in the meter (1 = none) | 1.0000 - |
| Meter reading difference | 1,500.0 kWh |
Applying the formula below gives:
| Result | Value |
|---|---|
| Installed CT ratio | 40.000 |
| Installed PT ratio | 100.00 |
| Multiplying factor | 4,000.0 |
| Actual energy | 6,000,000 kWh |
Open this example in the calculator and change any input.
Formula
\(k_{CT} = I_{1}/I_{2}, \quad k_{PT} = U_{1}/U_{2}\)
\(MF = \frac{k_{CT}\, k_{PT}}{k_{CT,m}\, k_{PT,m}}\)
\(E = MF \cdot \Delta R\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(I_{1}\) | CT primary current | A |
| \(I_{2}\) | CT secondary current | A |
| \(U_{1}\) | PT primary voltage | V |
| \(U_{2}\) | PT secondary voltage | V |
| \(k_{CT,m}\) | CT ratio programmed in the meter | - |
| \(k_{PT,m}\) | PT ratio programmed in the meter | - |
| \(\Delta R\) | meter reading difference | J |
| \(k_{CT}\) | installed CT ratio | - |
| \(k_{PT}\) | installed PT ratio | - |
| \(MF\) | multiplying factor | - |
| \(E\) | actual energy | J |
Method and standards
A transformer-operated meter sees secondary quantities; the multiplying factor restores primary energy. Whatever ratio is already programmed into the meter is divided out.
Where it is used
- Checking utility bills and sub-meter readings.
- Commissioning new HT meters.
- Reconciling plant energy balances.
Common mistakes
- Applying MF to a meter already programmed for primary readings.
- Using the wrong CT tap.
- Forgetting the PT ratio on HT meters.
Assumptions and limits
- Ideal CT and PT ratios; instrument transformer errors not included.
References
- MF = (CT ratio × PT ratio) / ratios set in the meter
Questions and answers
What is the MF of a meter on 200/5 A CTs and 11 kV/110 V PTs?
40 × 100 = 4 000, so 1 500 kWh on the meter is 6 000 MWh actually consumed (when the meter itself has no ratio programmed).
What if the meter is programmed with a different CT ratio?
Divide by what the meter already applies: a meter set to 100/5 on a 400/5 CT needs a factor of 4 for the CT.
Is MF needed on an LT meter without PTs?
Only the CT ratio: an 800/5 A CT meter has MF 160.
Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.