Worked example
Example: 3 200 imp/kWh, 32 pulses in 35.5 s at 1 kW. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Meter constant (impulses or revolutions per kWh) | 3,200.0 - |
| Pulses or revolutions counted | 32.000 - |
| Time taken | 35.500 s |
| True load during the test | 1,000.0 W |
Applying the formula below gives:
| Result | Value |
|---|---|
| Energy recorded by the meter | 0.010000 kWh |
| True energy | 0.009861 kWh |
| Meter error (positive = reads fast) | 1.4085 % |
| Time a correct meter would take | 36.000 s |
Open this example in the calculator and change any input.
Formula
\(E_m = \frac{n}{K}, \quad \varepsilon = \frac{E_m - P\, t}{P\, t}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(K\) | Meter constant (impulses or revolutions per kWh) | - |
| \(n\) | Pulses or revolutions counted | - |
| \(t\) | Time taken | s |
| \(P\) | True load during the test | W |
| \(E_m\) | Energy recorded by the meter | J |
| \(E_t\) | True energy | J |
| \(\varepsilon\) | Meter error (positive = reads fast) | - |
| \(t_0\) | Time a correct meter would take | s |
Method and standards
Recorded energy from the meter constant compared with the true energy.
Where it is used
- Site checks of tariff and sub-meters.
- Electrician practice.
Common mistakes
- Using the nameplate load as true load.
- Too few pulses.
Assumptions and limits
- Steady load during the test.
References
- Meter constant definition; error = (recorded − true) / true
Questions and answers
A 3200 imp/kWh meter gives 32 pulses in 35.5 s on a 1000 W load. What is its error?
Recorded 0.01 kWh; true 0.00986 kWh; error +1.4 %.
How long should the test be?
Long enough that one pulse of timing error is small: 30 or more pulses.
What is the true load?
From a reference meter or a known resistive load and measured voltage.
Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.