Worked example
Example: 200 A, 0.1 Ω/km, 500 m, three phase 415 V. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Line current | 200.00 A |
| Resistance of one conductor per unit length | 0.10000 Ω/km |
| Route length | 500.00 m |
| Supply | Three phase |
| Voltage (line to line for three phase) | 415.00 V |
| Power factor | 0.90000 - |
| Running time in the year | 6,000.0 h |
Applying the formula below gives:
| Result | Value |
|---|---|
| Power lost in the line | 6.0000 kW |
| Power carried | 129.38 kW |
| Loss as a share of the power carried | 4.6374 % |
| Energy lost in the year | 36,000 kWh |
Open this example in the calculator and change any input.
Formula
\(P_{loss} = 3\, I^2\, r\, L\ (3\phi), \quad 2\, I^2\, r\, L\ (1\phi)\)
\(E_{loss} = P_{loss}\, t\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(I\) | Line current | A |
| \(r\) | Resistance of one conductor per unit length | Ω/m |
| \(L\) | Route length | m |
| \(\text{phases}\) | Supply | - |
| \(V\) | Voltage (line to line for three phase) | V |
| \(\cos\varphi\) | Power factor | - |
| \(t\) | Running time in the year | s |
| \(P_{loss}\) | Power lost in the line | W |
| \(P\) | Power carried | W |
| \(p_{loss}\) | Loss as a share of the power carried | - |
| \(E_{loss}\) | Energy lost in the year | J |
Method and standards
Joule heating in each loaded conductor.
Where it is used
- Energy audits of distribution systems.
- Justifying a larger cable or correction.
Common mistakes
- Counting only one conductor.
- Using 20 °C resistance for a hot cable.
Assumptions and limits
- Balanced load; neutral unloaded.
- The annual energy assumes the same current for all the running hours; for a varying load multiply by the loss-load factor (mean of I² over peak I²) instead.
References
- Joule's law: 3 I² R (three phase)
- 2 I² R (single phase, go and return)
Questions and answers
What does 200 A lose over 500 m of 0.1 Ω/km cable, three phase?
6.0 kW, which over 6000 h is 36000 kWh.
How does power factor help?
Loss goes with current squared; raising the power factor from 0.8 to 0.95 cuts the loss by 29 %.
Which resistance?
At the operating temperature; hot conductors have about 20 % more than at 20 °C.
Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.