Worked example
Example: Copper 0.1 Ω at 20 °C to 90 °C, 100 A. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Resistance at the reference temperature | 0.10000 Ω |
| Reference temperature | 20.000 °C |
| Operating temperature | 90.000 °C |
| Temperature coefficient of resistance at T₁ (per K) | 0.003930 - |
| Current (for the loss) | 100.00 A |
Applying the formula below gives:
| Result | Value |
|---|---|
| Resistance at the operating temperature | 0.12751 Ω |
| Resistance ratio | 1.2751 |
| I²R loss at the reference temperature | 1.0000 kW |
| I²R loss at the operating temperature | 1.2751 kW |
Open this example in the calculator and change any input.
Formula
\(R_2 = R_1 [1 + \alpha_1 (T_2 - T_1)]\)
\(P = I^2 R\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(R_1\) | resistance at the reference temperature | Ω |
| \(T_1\) | reference temperature | K |
| \(T_2\) | operating temperature | K |
| \(\alpha_1\) | temperature coefficient at T₁ | 1/K |
| \(I\) | current | A |
| \(R_2\) | resistance at the operating temperature | Ω |
| \(R_2 / R_1\) | resistance ratio | - |
| \(P_1\) | I²R loss at T₁ | W |
| \(P_2\) | I²R loss at T₂ | W |
| \(P\) | I²R loss | W |
Method and standards
Metal resistance rises almost linearly with temperature; the coefficient α applies at the reference temperature T₁. The conductor maker gives α for the conductor material.
Where it is used
- Correcting cable resistance for voltage-drop and loss calculations at operating temperature.
- Correcting winding resistance tests.
- Estimating losses in hot busbars.
Common mistakes
- Using α at 20 °C with a different reference temperature.
- Mixing per-km and total resistances.
- Ignoring AC resistance in large cables.
Assumptions and limits
- Linear relation; fine over the normal operating range.
- DC resistance.
- α is the coefficient at the reference temperature T₁; a 20 °C value used with another T₁ is flagged (α₁ = α₂₀/[1 + α₂₀(T₁ − 20 °C)]).
References
- R₂ = R₁ [1 + α (T₂ − T₁)]
Questions and answers
How much does copper resistance rise from 20 °C to 90 °C?
About 27.5 % with α = 0.00393 per K: 0.1 Ω becomes 0.1275 Ω, and the I²R loss at 100 A rises from 1.0 to 1.28 kW.
Why correct winding resistance readings?
Motor and transformer winding resistances are measured cold and must be corrected to the reference temperature before comparing with test values.
Does this include AC effects?
No. It is DC resistance; skin and proximity effects add to the AC resistance of large conductors.
Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.