Cable Voltage Drop (IEC 60364)

Voltage drop and power loss of a copper or aluminium cable, three-phase or single-phase, by the IEC 60364-5-52 Annex G formula.

Thermal power plantProcess steam and utilitiesIEC 60364 (low-voltage installations)Electric motorElectrician and wireman licence examinations

Inputs

Examples: Motor feeder 3-phase 415 V, 100 A, 120 m, 35 mm² Cu, cos 0.85Single-phase 230 V, 16 A, 40 m, 2.5 mm² Cu, cos 13-phase 415 V, 250 A, 200 m, 185 mm² Al, cos 0.8

Annex G is for low-voltage installations up to 1 000 V.
0.08 mΩ/m is the IEC 60364-5-52 Annex G value when the cable data sheet gives none.

Results

Voltage drop in per cent of the phase voltage2.9478%
Voltage drop, line to neutral (single-phase: in the circuit)7.0629V
Voltage drop, line to line (single-phase: same as above)12.233V
Voltage at the load402.77V
Conductor resistance in service (one conductor)0.077143Ω
Power loss in the cable2.3143kW

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Motor feeder 3-phase 415 V, 100 A, 120 m, 35 mm² Cu, cos 0.85. The inputs, in the units selected above:

InputValue
SystemThree-phase
Nominal voltage (line-to-line for three-phase)415.00 V
Design current100.00 A
Cable length (one way)120.00 m
Conductor cross-section35.000 mm²
ConductorCopper
Load power factor0.85000 -
Reactance per unit length of conductor0.080000 mΩ/m

Applying the formula below gives:

ResultValue
Voltage drop in per cent of the phase voltage2.9478 %
Voltage drop, line to neutral (single-phase: in the circuit)7.0629 V
Voltage drop, line to line (single-phase: same as above)12.233 V
Voltage at the load402.77 V
Conductor resistance in service (one conductor)0.077143 Ω
Power loss in the cable2.3143 kW

Open this example in the calculator and change any input.

Formula

\(u = b\left(\rho_1\,\frac{L}{S}\cos\varphi + \lambda\,L\sin\varphi\right) I_b \qquad \Delta u = \frac{u}{U_0} \qquad U_0 = \frac{U_n}{\sqrt 3}\ \text{(three-phase)},\ U_n\ \text{(single-phase)}\)

\(R = \rho_1\,\frac{L}{S} \qquad u_{LL} = \sqrt 3\,u\ \text{(three-phase)} \qquad U_{load} = \sqrt 3\,(U_0 - u)\ \text{or}\ U_0 - u \qquad P_{loss} = n\,I_b^2 R\)

with \(b = 1\) and \(n = 3\) for three-phase, \(b = 2\) and \(n = 2\) for single-phase.

Variables

Symbol Meaning SI unit
\(\text{system}\) three-phase or single-phase –
\(U_n\) nominal voltage (line to line for three-phase) V
\(I_b\) design current A
\(L\) cable length, one way m
\(S\) conductor cross-section m²
\(\text{material}\) copper or aluminium –
\(\cos\varphi\) load power factor –
\(\lambda\) reactance per unit length of conductor Ω/m
\(\Delta u\) voltage drop in per cent of \(U_0\) –
\(u\) voltage drop, line to neutral (single-phase: in the circuit) V
\(u_{LL}\) voltage drop, line to line V
\(U_{load}\) voltage at the load V
\(R\) resistance of one conductor in service Ω
\(P_{loss}\) power loss in the cable W
\(\rho_1\) resistivity in service (Cu 0.0225, Al 0.036 Ω·mm²/m) Ω·m
\(U_0\) voltage between line and neutral V

Method and standards

IEC 60364-5-52:2009 Annex G (voltage drop in consumers' installations), including its resistivities in normal service and its default reactance of 0.08 mΩ/m.

Where it is used

  • Sizing motor and feeder cables in boiler houses and plants.
  • Checking long cable runs to pumps and fans.
  • Motor starting voltage dip checks.

Common mistakes

  • Using the cable resistance at 20 °C for a hot cable.
  • Forgetting the reactance on large cables.
  • Checking running current only when starting current sets the limit.

Assumptions and limits

  • Low-voltage circuits up to 1 000 V; balanced three-phase load.
  • Conductor at its normal service temperature (resistivity 1.25 × the 20 °C value); a lightly loaded cable has a smaller drop.
  • Steady running current; motor starting current gives a larger, short drop.
  • Use the cable maker's reactance where known, especially for single-core cables laid apart.
  • Lagging (inductive) or unity power factor only: sin φ is taken as positive. A leading (capacitive) load has a smaller drop than shown.
  • Drops above 3 % (lighting) and above 5 % (other uses) are flagged.

References

  • IEC 60364-5-52:2009 Annex G

Questions and answers

How is cable voltage drop calculated?

u = b(ρ₁·L·cosφ/S + λ·L·sinφ)·I, with b = 1 for three-phase and 2 for single-phase. A 120 m, 35 mm² copper feeder carrying 100 A at cos φ 0.85 drops 7.06 V per phase, 2.9 % of 240 V.

What resistivity is used?

The resistivity in normal service, 1.25 times the value at 20 °C: 0.0225 Ω·mm²/m for copper and 0.036 Ω·mm²/m for aluminium, as IEC 60364-5-52 Annex G gives them.

What voltage drop is allowed?

Annex G suggests 3 % for lighting and 5 % for other uses when supplied from a public low-voltage network, and 6 % and 8 % from a private supply. Motor starting and your specification may set tighter limits.

Method and article reviewed by FireCAD engineering on 10 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators