Transformer Full-Load Current (HV and LV)

Rated (full-load) current on the high-voltage and low-voltage sides of a three-phase or single-phase transformer from its kVA rating and voltages.

Thermal power plantProcess steam and utilities

Inputs

Examples: 1 000 kVA, 11 kV / 433 V2 500 kVA, 33 kV / 6.6 kV25 kVA single-phase, 11 kV / 240 V

Results

Primary rated current52.486A
Secondary rated current1,333.4A
Voltage ratio25.404

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 1 000 kVA, 11 kV / 433 V. The inputs, in the units selected above:

InputValue
Rated power1,000.0 kVA
Primary (HV) rated voltage, line to line11.000 kV
Secondary (LV) rated voltage, line to line433.00 V
SystemThree-phase

Applying the formula below gives:

ResultValue
Primary rated current52.486 A
Secondary rated current1,333.4 A
Voltage ratio25.404

Open this example in the calculator and change any input.

Formula

\(I_1 = \frac{S_r}{\sqrt 3\,U_1} \qquad I_2 = \frac{S_r}{\sqrt 3\,U_2} \qquad \text{(single-phase: without } \sqrt 3\text{)} \qquad \text{ratio} = \frac{U_1}{U_2}\)

Variables

Symbol Meaning SI unit
\(S_r\) rated power VA
\(U_1\) primary (HV) rated voltage, line to line V
\(U_2\) secondary (LV) rated voltage, line to line V
\(\text{system}\) three-phase or single-phase –
\(I_1\) primary rated current A
\(I_2\) secondary rated current A
\(U_1/U_2\) voltage ratio –

Method and standards

Rated current as defined in IEC 60076-1: the current flowing through a line terminal when rated power is applied at rated voltage.

Where it is used

  • Sizing cables and protection for transformers.
  • Checking transformer loading.
  • Plant electrical design.

Common mistakes

  • Using phase voltage instead of line voltage.
  • Mixing kVA and kW.
  • Using the wrong side's voltage.

Assumptions and limits

  • Balanced three-phase or single-phase transformer; for a three-winding transformer apply it to each winding with its own rating.
  • Rated (no-load) voltages; the current at a different operating voltage for the same kVA scales inversely.

References

  • IEC 60076-1 (rated current)

Questions and answers

What is the full-load current of a 1 000 kVA transformer?

At 11 kV / 433 V, 52.5 A on the 11 kV side and 1 333 A on the 433 V side: I = S/(√3·U).

Why 433 V and not 415 V?

Distribution transformers are often rated at 433 V no-load so that the voltage at the load, after the drop, is about 415 V. Use the rated voltage on the nameplate.

Is this the current the transformer can carry?

It is the rated current, which the transformer carries continuously at rated conditions (IEC 60076-1). Overload capability depends on the loading guide and the ambient temperature.

Method and article reviewed by FireCAD engineering on 10 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.