Transformer Voltage Regulation at Any Load and Power Factor

Voltage regulation of a transformer from its percentage resistance and reactance, the load and power factor (lagging or leading), with the secondary voltage.

Thermal power plantProcess steam and utilities

Inputs

Examples: 1.2 % R, 4.5 % X, full load, 0.8 laggingSame at 0.8 leading1 % R, 6 % X, 75 % load, unity

Results

Regulation is the fall from no-load to on-load voltage, as a share of the no-load (rated) voltage.

Percentage impedance4.6573%
Voltage regulation3.7015%
Secondary voltage on load416.97V
Voltage drop16.027V

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 1.2 % R, 4.5 % X, full load, 0.8 lagging. The inputs, in the units selected above:

InputValue
Percentage resistance (copper loss / rating)1.2000 %
Percentage reactance4.5000 %
Load as a share of rating100.00 %
Load power factor0.80000 -
Load isLagging (inductive)
No-load secondary voltage433.00 V

Applying the formula below gives:

ResultValue
Percentage impedance4.6573 %
Voltage regulation3.7015 %
Secondary voltage on load416.97 V
Voltage drop16.027 V

Open this example in the calculator and change any input.

Formula

\(\varepsilon = a(\varepsilon_r \cos\varphi \pm \varepsilon_x \sin\varphi) + \frac{[a(\varepsilon_x \cos\varphi \mp \varepsilon_r \sin\varphi)]^2}{2}\)

Variables

Symbol Meaning SI unit
\(\varepsilon_r\) Percentage resistance (copper loss / rating) -
\(\varepsilon_x\) Percentage reactance -
\(a\) Load as a share of rating -
\(\cos\varphi\) Load power factor -
\(\text{load}\) Load is -
\(V_{2,0}\) No-load secondary voltage V
\(\varepsilon_z\) Percentage impedance -
\(\varepsilon\) Voltage regulation -
\(V_2\) Secondary voltage on load V
\(\Delta V\) Voltage drop V

Method and standards

Per-unit phasor diagram of the equivalent circuit, expanded to second order (+ for lagging, − for leading).

Where it is used

  • Tap setting and voltage checks.
  • Electrical examinations.

Common mistakes

  • Using ε_z alone.
  • Wrong sign for leading loads.

Assumptions and limits

  • Per-unit values on the transformer rating.

References

  • Approximate regulation formula ε = a(ε_r cos φ + ε_x sin φ) + [a(ε_x cos φ − ε_r sin φ)]²/200 (in %; M.G. Say, Performance and Design of AC Machines)

Questions and answers

What is the regulation with 1.2 % resistance and 4.5 % reactance at full load, 0.8 lagging?

3.70 %, so a 433 V secondary gives 417.0 V.

Can regulation be negative?

Yes, with a leading load the voltage rises.

Where do ε_r and ε_x come from?

ε_r is the load loss over the rating; ε_x = √(ε_z² − ε_r²) from the nameplate impedance.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.