Worked example
Example: 1.2 % R, 4.5 % X, full load, 0.8 lagging. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Percentage resistance (copper loss / rating) | 1.2000 % |
| Percentage reactance | 4.5000 % |
| Load as a share of rating | 100.00 % |
| Load power factor | 0.80000 - |
| Load is | Lagging (inductive) |
| No-load secondary voltage | 433.00 V |
Applying the formula below gives:
| Result | Value |
|---|---|
| Percentage impedance | 4.6573 % |
| Voltage regulation | 3.7015 % |
| Secondary voltage on load | 416.97 V |
| Voltage drop | 16.027 V |
Open this example in the calculator and change any input.
Formula
\(\varepsilon = a(\varepsilon_r \cos\varphi \pm \varepsilon_x \sin\varphi) + \frac{[a(\varepsilon_x \cos\varphi \mp \varepsilon_r \sin\varphi)]^2}{2}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\varepsilon_r\) | Percentage resistance (copper loss / rating) | - |
| \(\varepsilon_x\) | Percentage reactance | - |
| \(a\) | Load as a share of rating | - |
| \(\cos\varphi\) | Load power factor | - |
| \(\text{load}\) | Load is | - |
| \(V_{2,0}\) | No-load secondary voltage | V |
| \(\varepsilon_z\) | Percentage impedance | - |
| \(\varepsilon\) | Voltage regulation | - |
| \(V_2\) | Secondary voltage on load | V |
| \(\Delta V\) | Voltage drop | V |
Method and standards
Per-unit phasor diagram of the equivalent circuit, expanded to second order (+ for lagging, − for leading).
Where it is used
- Tap setting and voltage checks.
- Electrical examinations.
Common mistakes
- Using ε_z alone.
- Wrong sign for leading loads.
Assumptions and limits
- Per-unit values on the transformer rating.
References
- Approximate regulation formula ε = a(ε_r cos φ + ε_x sin φ) + [a(ε_x cos φ − ε_r sin φ)]²/200 (in %; M.G. Say, Performance and Design of AC Machines)
Questions and answers
What is the regulation with 1.2 % resistance and 4.5 % reactance at full load, 0.8 lagging?
3.70 %, so a 433 V secondary gives 417.0 V.
Can regulation be negative?
Yes, with a leading load the voltage rises.
Where do ε_r and ε_x come from?
ε_r is the load loss over the rating; ε_x = √(ε_z² − ε_r²) from the nameplate impedance.
Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.