Worked example
Example: 1 MVA 11/0.415 kV. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Open-circuit test voltage (rated, LV side) | 415.00 V |
| Open-circuit current | 15.000 A |
| Open-circuit power (3 phases) | 2,200.0 W |
| Short-circuit test voltage (line, HV side) | 550.00 V |
| Short-circuit current | 52.500 A |
| Short-circuit power (3 phases) | 10,500 W |
| Rated HV line voltage | 11.000 kV |
| Rated power | 1,000.0 kVA |
Applying the formula below gives:
| Result | Value |
|---|---|
| Core-loss resistance per phase (LV, star) | 78.284 Ω |
| Magnetising reactance per phase (LV, star) | 16.317 Ω |
| Equivalent resistance per phase (HV, star) | 1.2698 Ω |
| Equivalent reactance per phase (HV, star) | 5.9136 Ω |
| Percentage impedance | 4.9987 % |
| Full-load copper loss | 10.495 kW |
Open this example in the calculator and change any input.
Formula
Per phase of the star equivalent, from line voltages and three-phase powers:
\(V_0 = \frac{V_{oc}}{\sqrt 3}, \ P_0 = \frac{P_{oc}}{3}, \ \cos\phi_0 = \frac{P_0}{V_0 I_{oc}}, \quad R_c = \frac{V_0^2}{P_0}, \ X_m = \frac{V_0}{I_{oc}\sin\phi_0}\)
\(Z_{eq} = \frac{V_{sc}/\sqrt 3}{I_{sc}}, \ R_{eq} = \frac{P_{sc}/3}{I_{sc}^2}, \ X_{eq} = \sqrt{Z_{eq}^2 - R_{eq}^2}, \quad z = \frac{Z_{eq} S}{V_{HV}^2}, \ P_{cu} = 3 I_r^2 R_{eq}, \ I_r = \frac{S}{\sqrt 3 V_{HV}}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(V_{oc}\) | Open-circuit test voltage (rated, LV side) | V |
| \(I_{oc}\) | Open-circuit current | A |
| \(P_{oc}\) | Open-circuit power (3 phases) | W |
| \(V_{sc}\) | Short-circuit test voltage (line, HV side) | V |
| \(I_{sc}\) | Short-circuit current | A |
| \(P_{sc}\) | Short-circuit power (3 phases) | W |
| \(V_{HV}\) | Rated HV line voltage | V |
| \(S\) | Rated power | VA |
| \(R_c\) | Core-loss resistance per phase (LV, star) | Ω |
| \(X_m\) | Magnetising reactance per phase (LV, star) | Ω |
| \(R_{eq}\) | Equivalent resistance per phase (HV, star) | Ω |
| \(X_{eq}\) | Equivalent reactance per phase (HV, star) | Ω |
| \(z\) | Percentage impedance | - |
| \(P_{cu}\) | Full-load copper loss | W |
| \(V_0, P_0\) | Open-circuit voltage and power per phase | V, W |
| \(\phi_0\) | No-load power-factor angle | rad |
| \(Z_{eq}\) | Equivalent impedance per phase (HV, star) | Ω |
| \(I_r\) | Rated HV line current | A |
Method and standards
Per-phase test analysis.
Where it is used
- Acceptance test evaluation.
- Building fault-study data.
Common mistakes
- Mixing line and phase values.
- Using three-phase power per phase.
Assumptions and limits
Three-phase transformer only: voltages are line values and powers the three-phase totals. For a single-phase transformer do not use this page: enter its readings in R_c = V²/P, X_m = V/(I sin φ₀), Z_eq = V/I, R_eq = P/I² directly, otherwise the results are off by √3 and 3.
Star equivalent; balanced test.
References
- Chapman
- Electric Machinery Fundamentals
- 5th ed. (McGraw-Hill, 2012)
- ch. 2 (transformer tests and equivalent circuit)
Questions and answers
Why test open-circuit on the LV side?
Rated voltage is easier to apply at low voltage, and the magnetising current is then a measurable size.
Why short-circuit on the HV side?
Rated current is smaller on the HV side and only a few per cent of rated voltage is needed.
What do the defaults represent?
A 1 MVA, 11/0.415 kV transformer with typical test readings.
Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.