FireCADCalc

Transformer Equivalent Circuit from Open- and Short-Circuit Tests

Transformer equivalent-circuit parameters, percentage impedance and full-load copper loss from open-circuit and short-circuit test readings.

Thermal power plantProcess steam and utilitiesSugar mill and cogenerationChemical and fertiliserPulp and paperFood, dairy and textile

Inputs

Examples: 1 MVA 11/0.415 kV2.5 MVA

Results

Three-phase transformer: line voltages and three-phase powers are converted to star-equivalent per-phase values (V/√3, P/3); a single-phase test entered here would be wrong by √3 and 3. If the short-circuit test was not at rated current, copper loss scales with current squared (done here via R_eq).

Core-loss resistance per phase (LV, star)78.284Ω
Magnetising reactance per phase (LV, star)16.317Ω
Equivalent resistance per phase (HV, star)1.2698Ω
Equivalent reactance per phase (HV, star)5.9136Ω
Percentage impedance4.9987%
Full-load copper loss10.495kW

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 1 MVA 11/0.415 kV. The inputs, in the units selected above:

InputValue
Open-circuit test voltage (rated, LV side)415.00 V
Open-circuit current15.000 A
Open-circuit power (3 phases)2,200.0 W
Short-circuit test voltage (line, HV side)550.00 V
Short-circuit current52.500 A
Short-circuit power (3 phases)10,500 W
Rated HV line voltage11.000 kV
Rated power1,000.0 kVA

Applying the formula below gives:

ResultValue
Core-loss resistance per phase (LV, star)78.284 Ω
Magnetising reactance per phase (LV, star)16.317 Ω
Equivalent resistance per phase (HV, star)1.2698 Ω
Equivalent reactance per phase (HV, star)5.9136 Ω
Percentage impedance4.9987 %
Full-load copper loss10.495 kW

Open this example in the calculator and change any input.

Formula

Per phase of the star equivalent, from line voltages and three-phase powers:

\(V_0 = \frac{V_{oc}}{\sqrt 3}, \ P_0 = \frac{P_{oc}}{3}, \ \cos\phi_0 = \frac{P_0}{V_0 I_{oc}}, \quad R_c = \frac{V_0^2}{P_0}, \ X_m = \frac{V_0}{I_{oc}\sin\phi_0}\)

\(Z_{eq} = \frac{V_{sc}/\sqrt 3}{I_{sc}}, \ R_{eq} = \frac{P_{sc}/3}{I_{sc}^2}, \ X_{eq} = \sqrt{Z_{eq}^2 - R_{eq}^2}, \quad z = \frac{Z_{eq} S}{V_{HV}^2}, \ P_{cu} = 3 I_r^2 R_{eq}, \ I_r = \frac{S}{\sqrt 3 V_{HV}}\)

Variables

Symbol Meaning SI unit
\(V_{oc}\) Open-circuit test voltage (rated, LV side) V
\(I_{oc}\) Open-circuit current A
\(P_{oc}\) Open-circuit power (3 phases) W
\(V_{sc}\) Short-circuit test voltage (line, HV side) V
\(I_{sc}\) Short-circuit current A
\(P_{sc}\) Short-circuit power (3 phases) W
\(V_{HV}\) Rated HV line voltage V
\(S\) Rated power VA
\(R_c\) Core-loss resistance per phase (LV, star) Ω
\(X_m\) Magnetising reactance per phase (LV, star) Ω
\(R_{eq}\) Equivalent resistance per phase (HV, star) Ω
\(X_{eq}\) Equivalent reactance per phase (HV, star) Ω
\(z\) Percentage impedance -
\(P_{cu}\) Full-load copper loss W
\(V_0, P_0\) Open-circuit voltage and power per phase V, W
\(\phi_0\) No-load power-factor angle rad
\(Z_{eq}\) Equivalent impedance per phase (HV, star) Ω
\(I_r\) Rated HV line current A

Method and standards

Per-phase test analysis.

Where it is used

  • Acceptance test evaluation.
  • Building fault-study data.

Common mistakes

  • Mixing line and phase values.
  • Using three-phase power per phase.

Assumptions and limits

  • Three-phase transformer only: voltages are line values and powers the three-phase totals. For a single-phase transformer do not use this page: enter its readings in R_c = V²/P, X_m = V/(I sin φ₀), Z_eq = V/I, R_eq = P/I² directly, otherwise the results are off by √3 and 3.

  • Star equivalent; balanced test.

References

  • Chapman
  • Electric Machinery Fundamentals
  • 5th ed. (McGraw-Hill, 2012)
  • ch. 2 (transformer tests and equivalent circuit)

Questions and answers

Why test open-circuit on the LV side?

Rated voltage is easier to apply at low voltage, and the magnetising current is then a measurable size.

Why short-circuit on the HV side?

Rated current is smaller on the HV side and only a few per cent of rated voltage is needed.

What do the defaults represent?

A 1 MVA, 11/0.415 kV transformer with typical test readings.

Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.