Worked example
Example: 1 000 kVA 5 % with 630 kVA 4 %, 1 500 kVA load. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Rating of transformer 1 | 1,000.0 kVA |
| Percentage impedance of transformer 1 | 5.0000 % |
| Rating of transformer 2 | 630.00 kVA |
| Percentage impedance of transformer 2 | 4.0000 % |
| Total load | 1,500.0 kVA |
Applying the formula below gives:
| Result | Value |
|---|---|
| Load on transformer 1 | 839.16 kVA |
| Load on transformer 2 | 660.84 kVA |
| Loading of transformer 1 | 83.916 % |
| Loading of transformer 2 | 104.90 % |
| Largest total load without overloading either | 1,430.0 kVA |
Open this example in the calculator and change any input.
Formula
\(S_{L1} = S\, \frac{S_1 / z_1}{S_1/z_1 + S_2/z_2}, \quad S_{max} = \min(z_1, z_2) \left(\frac{S_1}{z_1} + \frac{S_2}{z_2}\right)\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(S_1\) | Rating of transformer 1 | VA |
| \(z_1\) | Percentage impedance of transformer 1 | - |
| \(S_2\) | Rating of transformer 2 | VA |
| \(z_2\) | Percentage impedance of transformer 2 | - |
| \(S\) | Total load | VA |
| \(S_{L1}\) | Load on transformer 1 | VA |
| \(S_{L2}\) | Load on transformer 2 | VA |
| \(u_1\) | Loading of transformer 1 | - |
| \(u_2\) | Loading of transformer 2 | - |
| \(S_{max}\) | Largest total load without overloading either | VA |
Method and standards
Parallel impedances on a common base.
Where it is used
- Adding a transformer to a substation.
- Electrical examinations.
Common mistakes
- Sharing in proportion to rating only.
- Ignoring tap differences.
Assumptions and limits
- Same ratio, vector group and X/R.
References
- Load division in inverse proportion to ohmic impedance (M.G. Say; IEC 60076-8 application guide)
Questions and answers
How do 1000 kVA at 5 % and 630 kVA at 4 % share 1500 kVA?
839 kVA and 661 kVA: the 630 kVA unit is at 105 %.
Why is the smaller one overloaded?
Its lower percentage impedance makes it take more than its share.
What total is safe?
1430 kVA, when the lower-impedance unit reaches its rating.