Transformer EMF Equation: Turns, Flux and Core Area

EMF of transformer windings from frequency, turns, peak flux density and core area by E = 4.44 f N Φm, with the volts per turn and the secondary voltage.

Thermal power plantProcess steam and utilitiesElectrician and wireman licence examinations

Inputs

Examples: 50 Hz, 1.2 T, 150 cm², 2 750 and 108 turns60 Hz, 1.5 T, 40 cm², 600 and 60 turns50 Hz, 1.0 T, 25 cm², 414 and 43 turns

Results

The constant is √2 π = 4.443 for a sinusoidal flux; textbooks round it to 4.44.

Peak flux B_m A_c18.000mWb
Volts per turn3.9986V
Primary EMF10,996V
Secondary EMF431.85V

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 50 Hz, 1.2 T, 150 cm², 2 750 and 108 turns. The inputs, in the units selected above:

InputValue
Frequency50.000 Hz
Peak flux density in the core1.2000 T
Net core cross-section150.00 cm²
Primary turns2,750.0 -
Secondary turns108.00 -

Applying the formula below gives:

ResultValue
Peak flux B_m A_c18.000 mWb
Volts per turn3.9986 V
Primary EMF10,996 V
Secondary EMF431.85 V

Open this example in the calculator and change any input.

Formula

\(E = \sqrt 2\, \pi f N \Phi_m \approx 4.44\, f N \Phi_m, \quad \Phi_m = B_m A_c\)

Variables

Symbol Meaning SI unit
\(f\) Frequency 1/s
\(B_m\) Peak flux density in the core T
\(A_c\) Net core cross-section m²
\(N_1\) Primary turns -
\(N_2\) Secondary turns -
\(\Phi_m\) Peak flux B_m A_c Wb
\(E_t\) Volts per turn V
\(E_1\) Primary EMF V
\(E_2\) Secondary EMF V

Method and standards

RMS value of N dΦ/dt for a sinusoidal flux.

Where it is used

  • Winding design and rewinding.
  • Electrical examinations.

Common mistakes

  • Using RMS flux density.
  • Gross instead of net core area.

Assumptions and limits

  • No saturation check beyond a warning above 1.9 T; grain-oriented silicon steel saturates at about 1.7–1.9 T.

  • Sinusoidal flux; no leakage.

References

  • Faraday's law for sinusoidal flux: E = √2 π f N Φ_m

Questions and answers

What are the volts per turn at 50 Hz, 1.2 T and 150 cm²?

Flux 18 mWb: 3.999 V per turn.

How many turns for 11 kV?

About 2751.

Why does a 60 Hz transformer overheat on 50 Hz?

The same voltage needs 20 % more flux, which saturates the core.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.