Worked example
Example: 1 000 kVA, 1.7 kW / 10.5 kW losses, 75 % load at 0.9 pf, 16 h. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Rated power | 1,000.0 kVA |
| No-load (core) loss | 1.7000 kW |
| Load (copper) loss at rated current | 10.500 kW |
| Load as a share of rating | 75.000 % |
| Load power factor | 0.90000 - |
| Hours per day at that load (energised the rest of the day) | 16.000 h |
Applying the formula below gives:
| Result | Value |
|---|---|
| Efficiency at the load | 98.886 % |
| Total loss at the load | 7.6063 kW |
| Load share for maximum efficiency | 40.237 % |
| Maximum efficiency (same power factor) | 99.070 % |
| All-day efficiency | 98.763 % |
| Energy lost per year | 49,384 kWh |
Open this example in the calculator and change any input.
Formula
\(\eta = \frac{x S_r \cos\varphi}{x S_r \cos\varphi + P_0 + x^2 P_k}\)
\(x_{max} = \sqrt{P_0 / P_k}\)
\(\eta_{ad} = \frac{x S_r \cos\varphi\, t_L}{x S_r \cos\varphi\, t_L + P_0 \cdot 24\,\text{h} + x^2 P_k t_L}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(S_r\) | rated power | VA |
| \(P_0\) | no-load (core) loss | W |
| \(P_k\) | load loss at rated current | W |
| \(x\) | load as a share of rating | - |
| \(\cos\varphi\) | load power factor | - |
| \(t_L\) | hours per day at that load | s |
| \(\eta\) | efficiency at the load | - |
| \(P_L\) | total loss at the load | W |
| \(x_{max}\) | load for maximum efficiency | - |
| \(\eta_{max}\) | maximum efficiency | - |
| \(\eta_{ad}\) | all-day efficiency | - |
| \(E_L\) | energy lost per year | J |
Method and standards
No-load loss is constant whenever the transformer is energised; load loss varies with the square of the load current. Efficiency is output over output plus losses; maximum efficiency occurs where the two losses are equal. All-day efficiency counts 24 hours of core loss against the hours at load.
Where it is used
- Comparing transformer offers by loss capitalisation.
- Deciding whether to switch off lightly loaded parallel transformers.
- Estimating yearly transformer energy losses.
Common mistakes
- Using the load loss at a different reference temperature.
- Comparing efficiencies at different power factors.
- Forgetting the core loss runs all year.
Assumptions and limits
- Losses from the test report at reference temperature.
- Harmonic and stray losses not included.
- One load level per day; rest of the day energised at no load.
References
- Transformer loss model (no-load loss constant, load loss ∝ load²)
Questions and answers
How efficient is a 1 000 kVA transformer at 75 % load?
With 1.7 kW no-load and 10.5 kW load losses at 0.9 power factor, 98.9 %. It peaks at 99.07 % at about 40 % load, where load loss equals no-load loss.
What is all-day efficiency?
Energy out over energy in through a day, counting the core loss for all 24 hours; it matters for distribution transformers that are energised all day but loaded only part of it.
How much energy does the transformer waste in a year?
In the example about 49 400 kWh: the core loss runs all year and the load loss only when loaded.