Worked example
Example: 500 kVA, three periods. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Rating | 500.00 kVA |
| No-load (core) loss | 1.0000 kW |
| Full-load copper loss | 5.5000 kW |
| Load in period 1 (pu) | 100.00 % |
| Duration of period 1 | 6.0000 h |
| Power factor 1 | 80.000 % |
| Load in period 2 (pu) | 50.000 % |
| Duration of period 2 | 10.000 h |
| Power factor 2 | 85.000 % |
| Load in period 3 (pu) | 10.000 % |
| Duration of period 3 | 8.0000 h |
| Power factor 3 | 90.000 % |
| Load in period 4 (pu) | 0 % |
| Duration of period 4 | 0 h |
| Power factor 4 | 90.000 % |
Applying the formula below gives:
| Result | Value |
|---|---|
| Energy delivered per day | 4,885.0 kWh |
| Energy lost per day | 71.190 kWh |
| All-day efficiency | 98.564 % |
| Load fraction for maximum efficiency | 42.640 % |
Open this example in the calculator and change any input.
Formula
\(\eta_{ad} = \frac{\sum x_iS\cos\phi_it_i}{\sum x_iS\cos\phi_it_i + P_0 t_{day} + \sum x_i^2P_kt_i}, \quad x_{\eta,max} = \sqrt{\frac{P_0}{P_k}}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(S\) | Rating | VA |
| \(P_0\) | No-load (core) loss | W |
| \(P_k\) | Full-load copper loss | W |
| \(x_1\) | Load in period 1 (pu) | - |
| \(t_1\) | Duration of period 1 | s |
| \(\cos\phi_1\) | Power factor 1 | - |
| \(x_2\) | Load in period 2 (pu) | - |
| \(t_2\) | Duration of period 2 | s |
| \(\cos\phi_2\) | Power factor 2 | - |
| \(x_3\) | Load in period 3 (pu) | - |
| \(t_3\) | Duration of period 3 | s |
| \(\cos\phi_3\) | Power factor 3 | - |
| \(x_4\) | Load in period 4 (pu) | - |
| \(t_4\) | Duration of period 4 | s |
| \(\cos\phi_4\) | Power factor 4 | - |
| \(E_{out}\) | Energy delivered per day | J |
| \(E_{loss}\) | Energy lost per day | J |
| \(\eta_{ad}\) | All-day efficiency | - |
| \(x_{\eta,max}\) | Load fraction for maximum efficiency | - |
| \(t_{day}\) | One day (24 h) | s |
Method and standards
Energy balance.
Where it is used
- Transformer purchase evaluation.
- Energy audits of distribution networks.
Common mistakes
- Ignoring idle hours for core loss.
- Using full-load efficiency for energy.
Assumptions and limits
The transformer is energised all day: hours not covered by the periods count as no-load, with core loss only. The periods must not add to more than 24 h.
Constant load within each period.
References
- Chapman
- Electric Machinery Fundamentals
- 5th ed. (McGraw-Hill, 2012)
- ch. 2 (transformer efficiency; all-day efficiency)
Questions and answers
Why all-day efficiency?
A distribution transformer is energised all day but loaded only part of it; its energy efficiency matters more than its full-load efficiency.
When is efficiency highest?
At the load where copper loss equals core loss: x = √(P₀/P_k).
What do the defaults represent?
A 500 kVA transformer with 1 kW core and 5.5 kW copper loss on a three-period daily cycle.
Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.