Economic Conductor Size (Kelvin's Law)

Economic conductor size by Kelvin's law from load current, hours, energy price, conductor cost per mm²·km and capital charge, with current density.

Thermal power plantProcess steam and utilitiesSugar mill and cogenerationChemical and fertiliserPulp and paperFood, dairy and textile

Inputs

Examples: 400 A, 6,000 h, copper 8,000/mm²·kmAluminium 600 A, 7,500 h

Results

Kelvin's law: at the economic size the annual cost of losses equals the annual charge on the part of conductor cost proportional to area. Check thermal rating and voltage drop separately; IEC 60287-3-2 refines this with load growth and discounting.

Economic cross-section409.88mm²
Annual loss cost per km at A_econ1,180,449
Annual capital charge per km at A_econ1,180,449
Economic current density0.97590A/mm²

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 400 A, 6,000 h, copper 8,000/mm²·km. The inputs, in the units selected above:

InputValue
Load current (rms, per conductor)400.00 A
Equivalent full-load (loss-load) hours per year, Σ I²t / I²6,000.0 h
Energy cost per kWh8.0000 -
Conductor cost per mm² per km (variable part)8,000.0 -
Annual capital charge rate12.000 %
Resistivity at operating temperature2.1000e-08 Ω·m
Conductors per circuit3.0000 -

Applying the formula below gives:

ResultValue
Economic cross-section409.88 mm²
Annual loss cost per km at A_econ1,180,449
Annual capital charge per km at A_econ1,180,449
Economic current density0.97590 A/mm²

Open this example in the calculator and change any input.

Formula

\(A_{econ} = I\sqrt{\frac{\rho\,t_a\,c_e}{c_c\,r}}\ \text{(per conductor, consistent units)}, \quad C_{loss} = C_{cap}\)

Variables

Symbol Meaning SI unit
\(I\) Load current (rms, per conductor) A
\(t_a\) Equivalent full-load (loss-load) hours per year, Σ I²t / I² s
\(c_e\) Energy cost per kWh -
\(c_c\) Conductor cost per mm² per km (variable part) -
\(r\) Annual capital charge rate -
\(\rho\) Resistivity at operating temperature Ω·m
\(n\) Conductors per circuit -
\(A_{econ}\) Economic cross-section m²
\(C_{loss}\) Annual loss cost per km at A_econ -
\(C_{cap}\) Annual capital charge per km at A_econ -
\(J\) Economic current density A/m²

Method and standards

Kelvin's law.

Where it is used

  • Long, heavily loaded feeders and busducts.
  • Energy-efficiency cable sizing.

Common mistakes

  • Using peak instead of loss-equivalent hours.
  • Including fixed (installation) costs that do not scale with area.

Assumptions and limits

  • Cost linear in area. t_a is the loss-load (I²-weighted) equivalent hours, Σ I²t / I² for the I entered, not the operating hours.
  • Energy cost per kWh and conductor cost per mm² per km are converted to SI inside (per J and per m³ of conductor).

References

  • Kelvin's law for economic conductor size (annual loss cost = annual capital charge on the area-dependent cost)

Questions and answers

Why choose a larger conductor than thermal rating needs?

Losses go as 1/A; on heavily used circuits the saving in losses over the years exceeds the extra copper or aluminium.

What current density results?

Typically 0.5–1.5 A/mm² for copper with high utilisation, far below thermal limits.

What do the defaults represent?

A 400 A three-core circuit used 6,000 h/year at 8 per kWh, copper at 8,000 per mm²·km and a 12 % capital charge.

Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.