Busbar Size from Current Density

Cross-section and width of a copper or aluminium busbar for a current at a chosen current density and bar thickness, with the bars per phase.

Thermal power plantProcess steam and utilities

Inputs

Examples: 2 000 A at 1.2 A/mm², two 10 mm bars630 A at 1.6 A/mm², one 6 mm bar4 000 A at 0.8 A/mm², four 12 mm bars

Your design figure for the metal, enclosure and temperature rise; it decides the size.

Results

A first size only: the temperature rise depends on the enclosure, bar spacing and skin effect, and the short-circuit strength must be checked separately.

Cross-section needed per phase1,666.7mm²
Width of each bar83.333mm

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 2 000 A at 1.2 A/mm², two 10 mm bars. The inputs, in the units selected above:

InputValue
Current per phase2,000.0 A
Current density1.2000 A/mm²
Bar thickness10.000 mm
Bars per phase2.0000 -

Applying the formula below gives:

ResultValue
Cross-section needed per phase1,666.7 mm²
Width of each bar83.333 mm

Open this example in the calculator and change any input.

Formula

\(A = \frac{I}{J}, \quad w = \frac{A}{n\, t}\)

Variables

Symbol Meaning SI unit
\(I\) Current per phase A
\(J\) Current density A/m²
\(t\) Bar thickness m
\(n\) Bars per phase -
\(A\) Cross-section needed per phase m²
\(w\) Width of each bar m

Method and standards

Current density method.

Where it is used

  • Panel and bus duct first sizing.
  • Checking existing bars.

Common mistakes

  • Using an open-air density inside a sealed panel.
  • Ignoring short-circuit forces.

Assumptions and limits

  • Uniform current density, shared equally by the bars. In AC service several bars per phase share unevenly (proximity and skin effect); more than two bars per phase are flagged.

References

  • A = I / J (current density method)

Questions and answers

What busbar for 2000 A at 1.2 A/mm² with two 10 mm bars?

1667 mm², so two bars 83 mm wide: use the next standard width.

What current density should I use?

It depends on metal, ventilation and allowed rise; take it from your panel standard or the bar maker.

Is that enough?

No: check temperature rise by test or the maker's tables, and the fault withstand.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.