Worked example
Example: 105 kA peak, 100 mm, 0.6 m span, three phase. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Peak short-circuit current | 105.00 kA |
| Centre-to-centre spacing of the conductors | 100.00 mm |
| Span between supports | 0.60000 m |
| Arrangement | Three phase, side by side (centre conductor) |
Applying the formula below gives:
| Result | Value |
|---|---|
| Force per unit length | 19.096 kN/m |
| Force on one span | 11.458 kN |
Open this example in the calculator and change any input.
Formula
\(F' = \frac{\mu_0}{2\pi}\, \frac{i_p^2}{a}\ \left(\times \frac{\sqrt 3}{2}\ \text{three phase}\right), \quad F = F'\, l\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(i_p\) | Peak short-circuit current | A |
| \(a\) | Centre-to-centre spacing of the conductors | m |
| \(l\) | Span between supports | m |
| \(\text{type}\) | Arrangement | - |
| \(F'\) | Force per unit length | N/m |
| \(F\) | Force on one span | N |
Method and standards
Force between parallel current-carrying conductors.
Where it is used
- Busbar support spacing checks.
- Cable cleat selection.
Common mistakes
- Using RMS instead of peak current.
- Spacing in mm in an SI formula.
Assumptions and limits
- Thin parallel conductors; static force.
- No conductor-shape factor (k₁s of IEC 60865-1) for rectangular bars close together: the result is the basic force between line currents.
References
- Ampère's force law
- F' = μ₀ i² / (2π a); three-phase centre conductor factor √3/2 (the basic relation of IEC 60865-1)
Questions and answers
What force acts between busbars 100 mm apart at 105 kA peak, three phase?
19.1 kN/m; on a 0.6 m span 11.5 kN.
Which current?
The peak (making) current, about 2.1 to 2.5 times the RMS symmetrical fault current.
Why the √3/2?
It is the largest force on the centre bar of three in a three-phase fault.
Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.