Symmetrical Components of Three Unbalanced Phasors

Zero-, positive- and negative-sequence components of three unbalanced voltages or currents from their magnitudes and angles, with the unbalance factors.

Thermal power plantProcess steam and utilities

Inputs

Examples: 230∠0°, 220∠−120°, 240∠125°Single-phasing: 100∠0°, 100∠180°, 0Currents 50∠−30°, 40∠−160°, 45∠95°

Results

The same transform applies to currents: read the voltages as amperes. Angles are those of the phase-A sequence phasors; an angle is not shown when its component is zero.

Zero-sequence component6.2243V
Positive-sequence component229.80V
Negative-sequence component10.920V
Negative-sequence unbalance factor4.7521%
Zero-sequence unbalance factor2.7085%
Zero-sequence angle161.03°
Positive-sequence angle1.7387°
Negative-sequence angle-55.467°

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 230∠0°, 220∠−120°, 240∠125°. The inputs, in the units selected above:

InputValue
Phase A magnitude230.00 V
Phase A angle0 °
Phase B magnitude220.00 V
Phase B angle-120.00 °
Phase C magnitude240.00 V
Phase C angle125.00 °

Applying the formula below gives:

ResultValue
Zero-sequence component6.2243 V
Positive-sequence component229.80 V
Negative-sequence component10.920 V
Negative-sequence unbalance factor4.7521 %
Zero-sequence unbalance factor2.7085 %
Zero-sequence angle161.03 °
Positive-sequence angle1.7387 °
Negative-sequence angle-55.467 °

Open this example in the calculator and change any input.

Formula

\(V_0 = \tfrac13 (V_a + V_b + V_c), \quad V_1 = \tfrac13 (V_a + a V_b + a^2 V_c), \quad V_2 = \tfrac13 (V_a + a^2 V_b + a V_c), \quad a = 1\angle 120°\)

Variables

Symbol Meaning SI unit
\(V_a\) Phase A magnitude V
\(\theta_a\) Phase A angle rad
\(V_b\) Phase B magnitude V
\(\theta_b\) Phase B angle rad
\(V_c\) Phase C magnitude V
\(\theta_c\) Phase C angle rad
\(V_0\) Zero-sequence component V
\(V_1\) Positive-sequence component V
\(V_2\) Negative-sequence component V
\(V_2/V_1\) Negative-sequence unbalance factor -
\(V_0/V_1\) Zero-sequence unbalance factor -
\(\theta_0\) Zero-sequence angle rad
\(\theta_1\) Positive-sequence angle rad
\(\theta_2\) Negative-sequence angle rad

Method and standards

Fortescue's transformation with complex phasors.

Where it is used

  • Unbalanced fault analysis.
  • Motor protection and power quality.
  • Power system examinations.

Common mistakes

  • Angles in the wrong rotation.
  • Using line and phase values together.

Assumptions and limits

  • Sequence phasors are those of phase A; the angles θ₀, θ₁ and θ₂ are their arguments, measured from the same reference as the inputs. A zero component has no angle.

  • Phase order a–b–c.

References

  • C.L. Fortescue
  • Trans. AIEE 37 (1918) 1027 (method of symmetrical coordinates)

Questions and answers

What do balanced phasors give?

Only a positive-sequence component equal to the phase value; V₀ and V₂ are zero.

What is the operator a?

1∠120°: it turns a phasor by a third of a cycle.

Why does negative sequence matter?

It heats motor rotors: a few per cent of voltage unbalance causes a much larger current unbalance.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.