Worked example
Example: 230∠0°, 220∠−120°, 240∠125°. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Phase A magnitude | 230.00 V |
| Phase A angle | 0 ° |
| Phase B magnitude | 220.00 V |
| Phase B angle | -120.00 ° |
| Phase C magnitude | 240.00 V |
| Phase C angle | 125.00 ° |
Applying the formula below gives:
| Result | Value |
|---|---|
| Zero-sequence component | 6.2243 V |
| Positive-sequence component | 229.80 V |
| Negative-sequence component | 10.920 V |
| Negative-sequence unbalance factor | 4.7521 % |
| Zero-sequence unbalance factor | 2.7085 % |
| Zero-sequence angle | 161.03 ° |
| Positive-sequence angle | 1.7387 ° |
| Negative-sequence angle | -55.467 ° |
Open this example in the calculator and change any input.
Formula
\(V_0 = \tfrac13 (V_a + V_b + V_c), \quad V_1 = \tfrac13 (V_a + a V_b + a^2 V_c), \quad V_2 = \tfrac13 (V_a + a^2 V_b + a V_c), \quad a = 1\angle 120°\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(V_a\) | Phase A magnitude | V |
| \(\theta_a\) | Phase A angle | rad |
| \(V_b\) | Phase B magnitude | V |
| \(\theta_b\) | Phase B angle | rad |
| \(V_c\) | Phase C magnitude | V |
| \(\theta_c\) | Phase C angle | rad |
| \(V_0\) | Zero-sequence component | V |
| \(V_1\) | Positive-sequence component | V |
| \(V_2\) | Negative-sequence component | V |
| \(V_2/V_1\) | Negative-sequence unbalance factor | - |
| \(V_0/V_1\) | Zero-sequence unbalance factor | - |
| \(\theta_0\) | Zero-sequence angle | rad |
| \(\theta_1\) | Positive-sequence angle | rad |
| \(\theta_2\) | Negative-sequence angle | rad |
Method and standards
Fortescue's transformation with complex phasors.
Where it is used
- Unbalanced fault analysis.
- Motor protection and power quality.
- Power system examinations.
Common mistakes
- Angles in the wrong rotation.
- Using line and phase values together.
Assumptions and limits
Sequence phasors are those of phase A; the angles θ₀, θ₁ and θ₂ are their arguments, measured from the same reference as the inputs. A zero component has no angle.
Phase order a–b–c.
References
- C.L. Fortescue
- Trans. AIEE 37 (1918) 1027 (method of symmetrical coordinates)
Questions and answers
What do balanced phasors give?
Only a positive-sequence component equal to the phase value; V₀ and V₂ are zero.
What is the operator a?
1∠120°: it turns a phasor by a third of a cycle.
Why does negative sequence matter?
It heats motor rotors: a few per cent of voltage unbalance causes a much larger current unbalance.