Peak and Asymmetrical Fault Current from the X/R Ratio

Peak (first-cycle) short-circuit current and the asymmetrical rms current at a time from the symmetrical fault current and the X/R ratio of the source.

Thermal power plantProcess steam and utilitiesSugar mill and cogenerationChemical and fertiliserPulp and paperFood, dairy and textile

Inputs

Examples: 25 kA, X/R 14, 50 ms40 kA near generator X/R 40, 30 ms

Results

κ = 1.02 + 0.98e^(−3R/X) is the widely used approximation (IEC 60909 form). Breaker making capacity must exceed the peak; breaking capacity is checked at contact parting with the DC component.

Peak factor1.8110
Peak current64.028kA
DC time constant0.044563s
DC component at t11.513kA
Asymmetrical rms current at t27.523kA

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 25 kA, X/R 14, 50 ms. The inputs, in the units selected above:

InputValue
Symmetrical rms fault current25.000 kA
X/R ratio at the fault14.000 -
Frequency50.000 Hz
Time after fault inception0.050000 s

Applying the formula below gives:

ResultValue
Peak factor1.8110
Peak current64.028 kA
DC time constant0.044563 s
DC component at t11.513 kA
Asymmetrical rms current at t27.523 kA

Open this example in the calculator and change any input.

Formula

\(\kappa = 1.02 + 0.98e^{-3/(X/R)}, \quad i_p = \kappa\sqrt2I_k, \quad I_{asym}(t) = \sqrt{I_k^2 + \left(\sqrt2I_ke^{-t/\tau}\right)^2}\)

Variables

Symbol Meaning SI unit
\(I_k\) Symmetrical rms fault current A
\(X/R\) X/R ratio at the fault -
\(f\) Frequency 1/s
\(t\) Time after fault inception s
\(\kappa\) Peak factor -
\(i_p\) Peak current A
\(\tau\) DC time constant s
\(I_{dc}(t)\) DC component at t A
\(I_{asym}(t)\) Asymmetrical rms current at t A

Method and standards

DC offset relations.

Where it is used

  • Breaker and busbar ratings.
  • CT saturation checks.

Common mistakes

  • Using symmetrical current for making duty.
  • Ignoring motor contribution.

Assumptions and limits

  • Fault at the worst instant; constant AC component.

References

  • Short-circuit current with DC offset: peak factor κ = 1.02 + 0.98e^(−3R/X)
  • DC decay with τ = X/(ωR)

Questions and answers

Why is the first peak higher than √2·I_k?

A fault starting near voltage zero adds a decaying DC offset; with high X/R it decays slowly and nearly doubles the first peak.

Where is X/R high?

Near large generators and transformers (X/R 15–50); low at the end of long cable feeders.

What do the defaults represent?

A 25 kA fault with X/R 14 at 50 Hz, checked at 50 ms.

Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.