Current Transformer Knee-Point Voltage Requirement

Minimum knee-point voltage of a protection CT for a through fault from secondary current, CT winding, lead and relay resistance and a transient factor.

Thermal power plantProcess steam and utilitiesSugar mill and cogenerationChemical and fertiliserPulp and paperFood, dairy and textile

Inputs

Examples: 400/1, 20 kA, earth fault loop1000/1, 31.5 kA, three-phase, K 1

Results

The factor K covers DC offset and remanence and comes from the relay maker (often 1–2 for overcurrent, larger for differential schemes, up to 1 + X/R for full offset without saturation).

Secondary fault current50.000A
Total secondary resistance2.6000Ω
Required knee-point voltage260.00V

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 400/1, 20 kA, earth fault loop. The inputs, in the units selected above:

InputValue
Maximum through-fault current (primary)20.000 kA
CT ratio (primary/secondary)400.00 -
CT secondary winding resistance1.5000 Ω
One-way lead resistance0.50000 Ω
Relay burden resistance0.10000 Ω
Lead loopTwo leads (earth fault)
Transient dimensioning factor2.0000 -

Applying the formula below gives:

ResultValue
Secondary fault current50.000 A
Total secondary resistance2.6000 Ω
Required knee-point voltage260.00 V

Open this example in the calculator and change any input.

Formula

\(V_k \ge K\frac{I_f}{CT}(R_{CT} + nR_L + R_r)\)

Variables

Symbol Meaning SI unit
\(I_f\) Maximum through-fault current (primary) A
\(CT\) CT ratio (primary/secondary) -
\(R_{CT}\) CT secondary winding resistance Ω
\(R_L\) One-way lead resistance Ω
\(R_r\) Relay burden resistance Ω
\(\text{leads}\) Lead loop -
\(K\) Transient dimensioning factor -
\(I_s\) Secondary fault current A
\(R_{total}\) Total secondary resistance Ω
\(V_k\) Required knee-point voltage V

Method and standards

Secondary circuit voltage.

Where it is used

  • Protection CT specification.
  • Checking CTs on uprated switchboards.

Common mistakes

  • Using rated burden VA instead of resistance.
  • Forgetting the return lead.

Assumptions and limits

  • Resistive burden.
  • The result is only as good as K: take it from the relay maker's CT requirement for the protection type (the note gives typical ranges).

References

  • CT secondary voltage requirement V_k ≥ K·I_s(R_CT + R_L + R_relay) (protection practice; relay makers' guides)

Questions and answers

What is the knee point?

The secondary voltage above which a 10 % rise in voltage needs a 50 % rise in magnetising current: the CT is starting to saturate.

Why two leads for earth faults?

Earth-fault current returns through the neutral lead too, so the loop is go and return.

What do the defaults represent?

A 400/1 CT seeing a 20 kA through fault with 1.5 Ω winding, 0.5 Ω leads and 0.1 Ω relay.

Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.