Worked example
Example: 400/1, 20 kA, earth fault loop. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Maximum through-fault current (primary) | 20.000 kA |
| CT ratio (primary/secondary) | 400.00 - |
| CT secondary winding resistance | 1.5000 Ω |
| One-way lead resistance | 0.50000 Ω |
| Relay burden resistance | 0.10000 Ω |
| Lead loop | Two leads (earth fault) |
| Transient dimensioning factor | 2.0000 - |
Applying the formula below gives:
| Result | Value |
|---|---|
| Secondary fault current | 50.000 A |
| Total secondary resistance | 2.6000 Ω |
| Required knee-point voltage | 260.00 V |
Open this example in the calculator and change any input.
Formula
\(V_k \ge K\frac{I_f}{CT}(R_{CT} + nR_L + R_r)\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(I_f\) | Maximum through-fault current (primary) | A |
| \(CT\) | CT ratio (primary/secondary) | - |
| \(R_{CT}\) | CT secondary winding resistance | Ω |
| \(R_L\) | One-way lead resistance | Ω |
| \(R_r\) | Relay burden resistance | Ω |
| \(\text{leads}\) | Lead loop | - |
| \(K\) | Transient dimensioning factor | - |
| \(I_s\) | Secondary fault current | A |
| \(R_{total}\) | Total secondary resistance | Ω |
| \(V_k\) | Required knee-point voltage | V |
Method and standards
Secondary circuit voltage.
Where it is used
- Protection CT specification.
- Checking CTs on uprated switchboards.
Common mistakes
- Using rated burden VA instead of resistance.
- Forgetting the return lead.
Assumptions and limits
- Resistive burden.
- The result is only as good as K: take it from the relay maker's CT requirement for the protection type (the note gives typical ranges).
References
- CT secondary voltage requirement V_k ≥ K·I_s(R_CT + R_L + R_relay) (protection practice; relay makers' guides)
Questions and answers
What is the knee point?
The secondary voltage above which a 10 % rise in voltage needs a 50 % rise in magnetising current: the CT is starting to saturate.
Why two leads for earth faults?
Earth-fault current returns through the neutral lead too, so the loop is go and return.
What do the defaults represent?
A 400/1 CT seeing a 20 kA through fault with 1.5 Ω winding, 0.5 Ω leads and 0.1 Ω relay.
Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.