Worked example
Example: 2 MW LV motors at 415 V. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Total running motor power | 2,000.0 kW |
| Bus line voltage | 415.00 V |
| Efficiency × power factor | 80.000 % |
| Locked-rotor current ratio | 6.0000 - |
| Decay time constant | 0.030000 s |
| Time after fault | 0.020000 s |
Applying the formula below gives:
| Result | Value |
|---|---|
| Total rated current | 3,478.0 A |
| Initial motor contribution | 20.868 kA |
| Contribution at t | 10.714 kA |
Open this example in the calculator and change any input.
Formula
\(I_r = \frac{P}{\sqrt3V\eta\cos\phi}, \quad I_m(t) = \frac{I_{LR}}{I_r}I_re^{-t/\tau}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(P\) | Total running motor power | W |
| \(V\) | Bus line voltage | V |
| \(\eta\cos\phi\) | Efficiency × power factor | - |
| \(I_{LR}/I_r\) | Locked-rotor current ratio | - |
| \(\tau\) | Decay time constant | s |
| \(t\) | Time after fault | s |
| \(I_r\) | Total rated current | A |
| \(I_m(0)\) | Initial motor contribution | A |
| \(I_m(t)\) | Contribution at t | A |
Method and standards
Locked-rotor approximation.
Where it is used
- LV switchboard ratings.
- MCC breaker selection.
Common mistakes
- Ignoring motors in short-circuit studies.
- Counting standby motors.
Assumptions and limits
- Running motors only. The symmetrical AC envelope only: the DC offset that adds to the peak (making duty) is not included.
- τ is the motor's open-circuit subtransient decay, X″/(ωR_r) from the maker; typically a few cycles for LV motors, longer for large HV motors.
References
- Motor contribution approximated by locked-rotor current with exponential decay (definitions; Chapman, Electric Machinery Fundamentals, 5th ed. (McGraw-Hill, 2012))
Questions and answers
Why do motors feed a fault?
Their rotors keep spinning and their trapped flux makes them act briefly as generators.
How large is it?
About 4–6 times the total motor rated current for the first cycle.
What do the defaults represent?
2 MW of running LV motors on a 415 V bus.
Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.