Worked example
Example: 110 A motor, 6.5 x FLC, 180 % LRT, DOL. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Full-load current | 110.00 A |
| Locked-rotor current as a multiple of full-load current | 6.5000 - |
| Locked-rotor torque as a share of full-load torque | 180.00 % |
| Starting method | Direct on line (DOL) |
| Autotransformer tap (share of line voltage) | 65.000 % |
Applying the formula below gives:
| Result | Value |
|---|---|
| Starting current drawn from the line | 715.00 A |
| Starting current as a share of DOL current | 100.00 % |
| Starting torque as a share of full-load torque | 180.00 % |
| Voltage at the motor as a share of line voltage | 100.00 % |
Open this example in the calculator and change any input.
Formula
\(I_{DOL} = k I_{FL}\)
\(\text{star-delta: } I_{st} = I_{DOL}/3, \; T_{st} = T_{LR}/3\)
\(\text{autotransformer: } I_{st} = a^2 I_{DOL}, \; T_{st} = a^2 T_{LR}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(I_{FL}\) | full-load current | A |
| \(k\) | locked-rotor current multiple | - |
| \(T_{LR}\) | locked-rotor torque as a share of full-load torque | - |
| \(\text{method}\) | starting method | - |
| \(a\) | autotransformer tap | - |
| \(I_{DOL}\) | direct-on-line starting current | A |
| \(I_{st}\) | line starting current | A |
| \(I_{st} / I_{DOL}\) | starting current as a share of DOL | - |
| \(T_{st}\) | starting torque as a share of full-load torque | - |
| \(U_m / U\) | voltage at the motor as a share of line voltage | - |
Method and standards
Locked-rotor current is proportional to the voltage across the windings and torque to its square. Star connection puts 1/√3 of line voltage on each winding; an autotransformer at tap a puts a times line voltage on the motor and, neglecting magnetising current, draws a² of the DOL current from the line.
Where it is used
- Choosing a starter for a large pump or fan motor.
- Checking whether the motor can still start its load.
- Estimating starting current for voltage-dip and generator studies.
Common mistakes
- Choosing star-delta for a load with high breakaway torque (it may not start).
- Ignoring the current spike at the star-to-delta changeover.
- Taking full-load current as the starting current.
Assumptions and limits
- Steady locked-rotor values; transients and magnetising current not included. The DOL current I_DOL is given in a note.
- An open-transition star-delta changeover can draw a peak above the DOL current; it is not included.
- Soft starters and VFDs limit current by control, not by a fixed ratio.
References
- Reduced-voltage starting relations (current and torque ∝ voltage², star 1/√3)
Questions and answers
What starting current does a 110 A motor draw DOL?
With 6.5 times full-load locked-rotor current, 715 A. Star-delta cuts it to a third, about 238 A, but also cuts starting torque to a third.
Why does star-delta cut current and torque to a third?
Each winding sees 1/√3 of line voltage in star; winding current and torque fall by 1/√3 and 1/3, and line current in star is a third of the delta DOL value.
What does an autotransformer at 65 % do?
The motor gets 65 % voltage, so its torque and the line current both fall to 0.65², about 42 % of DOL.
Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.