Worked example
Example: 4-pole 415 V at 3 % slip. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Line voltage (parameters per phase of the star equivalent, V/√3) | 415.00 V |
| Frequency | 50.000 Hz |
| Poles | 4.0000 - |
| Stator resistance per phase | 0.20000 Ω |
| Stator leakage reactance | 0.60000 Ω |
| Rotor resistance referred to stator | 0.25000 Ω |
| Rotor leakage reactance referred | 0.60000 Ω |
| Magnetising reactance | 20.000 Ω |
| Slip | 3.0000 % |
Applying the formula below gives:
| Result | Value |
|---|---|
| Torque at the slip | 116.33 N·m |
| Stator current | 30.039 A |
| Power factor | 0.87138 |
| Breakdown torque | 372.32 N·m |
| Slip at breakdown | 20.846 % |
| Starting torque | 161.97 N·m |
Open this example in the calculator and change any input.
Formula
\(T = \frac{3V_{th}^2R'_2/s}{\omega_s\left[(R_{th} + R'_2/s)^2 + (X_{th} + X'_2)^2\right]}, \quad s_{max} = \frac{R'_2}{\sqrt{R_{th}^2 + (X_{th} + X'_2)^2}}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(V\) | Line voltage (parameters per phase of the star equivalent, V/√3) | V |
| \(f\) | Frequency | 1/s |
| \(p\) | Poles | - |
| \(R_1\) | Stator resistance per phase | Ω |
| \(X_1\) | Stator leakage reactance | Ω |
| \(R'_2\) | Rotor resistance referred to stator | Ω |
| \(X'_2\) | Rotor leakage reactance referred | Ω |
| \(X_m\) | Magnetising reactance | Ω |
| \(s\) | Slip | - |
| \(T\) | Torque at the slip | N·m |
| \(I_1\) | Stator current | A |
| \(\cos\phi\) | Power factor | - |
| \(T_{max}\) | Breakdown torque | N·m |
| \(s_{max}\) | Slip at breakdown | - |
| \(T_{st}\) | Starting torque | N·m |
Method and standards
Equivalent circuit.
Where it is used
- Motor selection for high-inertia starts.
- Teaching motor behaviour.
Common mistakes
- Line voltage in per-phase formulas.
- Rotor values not referred to the stator.
Assumptions and limits
- Constant parameters (no saturation or deep-bar effect).
- Parameters per phase of the star equivalent with phase voltage V/√3; convert delta-connected test data to star first (divide impedances by 3).
- Poles an even whole number. When the breakdown slip exceeds 1 it is shown as 100 % and a note explains that T_max is not reached in motoring.
References
- Chapman
- Electric Machinery Fundamentals
- 5th ed. (McGraw-Hill, 2012)
- ch. 6 (induction motor equivalent circuit and torque–speed characteristic)
Questions and answers
What sets breakdown torque?
Mostly the leakage reactances; rotor resistance changes the slip at which it occurs, not its value.
Why add rotor resistance for starting?
It moves breakdown towards standstill, raising starting torque (slip-ring motors, deep-bar rotors).
What do the defaults represent?
A 4-pole, 415 V motor with typical small-motor parameters at 3 % slip.
Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.