Synchronous Machine Power–Angle and Pull-Out Power

Active and reactive power of a round-rotor synchronous machine from internal EMF, bus voltage, synchronous reactance and load angle, with pull-out power.

Thermal power plantProcess steam and utilitiesSugar mill and cogenerationChemical and fertiliserPulp and paperFood, dairy and textile

Inputs

Examples: 13 kV EMF, 11 kV bus, 12 Ω, 30°Under-excited 10 kV, 60°

Results

Round rotor, resistance neglected, line values (P = EV sin δ/X_s for three phases with line voltages). Salient-pole machines add a reluctance term.

Active power5.9583MW
Reactive power to the bus0.23680Mvar
Pull-out (steady-state limit) power11.917MW
Stability margin2.0000

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 13 kV EMF, 11 kV bus, 12 Ω, 30°. The inputs, in the units selected above:

InputValue
Internal EMF (line value)13.000 kV
Terminal (bus) line voltage11.000 kV
Synchronous reactance per phase12.000 Ω
Load angle30.000 °

Applying the formula below gives:

ResultValue
Active power5.9583 MW
Reactive power to the bus0.23680 Mvar
Pull-out (steady-state limit) power11.917 MW
Stability margin2.0000

Open this example in the calculator and change any input.

Formula

\(P = \frac{EV}{X_s}\sin\delta, \quad Q = \frac{EV\cos\delta - V^2}{X_s}, \quad P_{max} = \frac{EV}{X_s}\)

Variables

Symbol Meaning SI unit
\(E\) Internal EMF (line value) V
\(V\) Terminal (bus) line voltage V
\(X_s\) Synchronous reactance per phase Ω
\(\delta\) Load angle rad
\(P\) Active power W
\(Q\) Reactive power to the bus var
\(P_{max}\) Pull-out (steady-state limit) power W
\(P_{max}/P\) Stability margin -

Method and standards

Round-rotor power–angle relation.

Where it is used

  • Captive generator operation.
  • Synchronous motor loading.

Common mistakes

  • Mixing phase and line values.
  • Using it for salient-pole machines unchanged.

Assumptions and limits

  • Round rotor, armature resistance neglected, line values for three phases. At zero load angle P is zero and the margin P_max/P is unbounded, so the page leaves it out.

  • Infinite bus; resistance neglected.

References

  • Chapman
  • Electric Machinery Fundamentals
  • 5th ed. (McGraw-Hill, 2012)
  • ch. 4 (power and torque in synchronous machines)

Questions and answers

What happens at 90°?

Power is at its maximum; any more load and the machine pulls out of step.

Why does excitation matter for stability?

Higher E raises P_max; an under-excited machine operates nearer its limit.

What do the defaults represent?

An 11 kV generator with 13 kV internal EMF, 12 Ω synchronous reactance and a 30° load angle.

Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.