Worked example
Example: 1600 kVA, 6 % Z, 250 MVA source; 250 kW motor, 6 x FLC. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Transformer rating | 1,600.0 kVA |
| Transformer impedance | 6.0000 % |
| Upstream fault level at the transformer primary | 250.00 MVA |
| Motor rated output | 250.00 kW |
| Motor efficiency | 95.000 % |
| Motor full-load power factor | 88.000 % |
| Starting current, multiple of full-load current | 6.0000 - |
Applying the formula below gives:
| Result | Value |
|---|---|
| Voltage dip at the bus | 6.9301 % |
| Motor starting kVA | 1,794.3 kVA |
| Short-circuit kVA at the bus | 24.096 MVA |
Open this example in the calculator and change any input.
Formula
\(S_{sc} = \left(\frac{z_T}{S_T} + \frac{1}{S_{src}}\right)^{-1} \qquad S_{st} = k\,\frac{P_m}{\eta\cos\varphi} \qquad \Delta V = \frac{S_{st}}{S_{st} + S_{sc}}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(S_T\) | transformer rating | VA |
| \(z_T\) | transformer impedance | – |
| \(S_{src}\) | source fault level | VA |
| \(P_m\) | motor rated output | W |
| \(\eta\) | motor efficiency | – |
| \(\cos\varphi\) | full-load power factor | – |
| \(k\) | starting current multiple | – |
| \(\Delta V\) | voltage dip | – |
| \(S_{st}\) | motor starting kVA | VA |
| \(S_{sc}\) | short-circuit kVA at the bus | VA |
Method and standards
Approximate kVA (impedance) method: the starting motor and the source impedance form a divider; angles are neglected, which slightly overstates the dip.
Where it is used
- Checking whether large feed pump and fan motors can start DOL.
- Choosing starter type.
- Transformer sizing for large motors.
Common mistakes
- Ignoring other load already on the bus.
- Using full-load instead of locked-rotor kVA.
- Forgetting cable impedance to the motor.
Assumptions and limits
- Infinite-bus approximation beyond the source fault level; resistances and angles neglected.
- The cable from the bus to the motor and any load already on the bus are not included: the dip at the motor terminals is larger than the bus dip shown.
References
- kVA (impedance) method for motor starting
Questions and answers
How much does the voltage dip when a big motor starts?
A 250 kW motor drawing 6 times full-load current takes about 1790 kVA at start; on a 1600 kVA, 6 % transformer fed from a 250 MVA source (24 MVA at the bus) the voltage dips about 6.9 %.
How much dip is acceptable?
Typically 10–15 % at the motor and less at other loads; contactors and drives may drop out at deeper dips. Check your plant's criteria.
How do I reduce it?
Star-delta, soft starter or VFD; a larger or lower-impedance transformer; or starting the motor from a stiffer bus.
Method and article reviewed by FireCAD engineering on 11 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.