Worked example
Example: 12 kg·m², 1 480 rpm, 700 and 250 N·m. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Total moment of inertia at the motor shaft | 12.000 kg·m² |
| Final speed | 1,480.0 rpm |
| Average motor torque during the start | 700.00 N·m |
| Average load torque during the start | 250.00 N·m |
Applying the formula below gives:
| Result | Value |
|---|---|
| Average accelerating torque | 450.00 N·m |
| Starting time | 4.1329 s |
| Kinetic energy at full speed | 144.12 kJ |
Open this example in the calculator and change any input.
Formula
\(t_s = \frac{J\, \omega}{T_m - T_l}, \quad \omega = 2\pi N, \quad E_k = \tfrac12 J \omega^2\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(J\) | Total moment of inertia at the motor shaft | kg·m² |
| \(N\) | Final speed | 1/s |
| \(T_m\) | Average motor torque during the start | N·m |
| \(T_l\) | Average load torque during the start | N·m |
| \(T_a\) | Average accelerating torque | N·m |
| \(t_s\) | Starting time | s |
| \(E_k\) | Kinetic energy at full speed | J |
Method and standards
Constant average accelerating torque.
Where it is used
- Large fans, centrifuges and mills.
- Setting overload relay classes.
Common mistakes
- Leaving out the load inertia.
- Inertia not referred through the gear ratio.
Assumptions and limits
- Average torques; no voltage dip. The average-torque method can be unconservative when the load curve approaches the motor curve near pull-up (fans): integrate over the torque–speed curves step by step in that case.
References
- Newton's second law for rotation
- J dω/dt = T_m − T_l
Questions and answers
How long to reach 1480 rpm with 12 kg·m², 700 N·m motor and 250 N·m load torque?
4.1 s.
Where do the average torques come from?
From the motor and load torque–speed curves; a common estimate for a DOL start is the mean of starting and pull-out torque.
Why does it matter?
Fans with high inertia can start for 20 s or more and trip thermal protection.
Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.