Worked example
Example: 55 kW at 75 %, 92 % to 95 %, 8000 h, 8/kWh. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Motor rated output | 55.000 kW |
| Load factor (shaft load / rating) | 75.000 % |
| Efficiency of the existing motor at that load | 92.000 % |
| Efficiency of the new motor at that load | 95.000 % |
| Running hours per year | 8,000.0 h |
| Energy price per kWh (your currency) | 8.0000 - |
| Extra cost of the new motor (your currency) | 150,000 - |
Applying the formula below gives:
| Result | Value |
|---|---|
| Input power saved | 1.4159 kW |
| Energy saved per year | 11,327 kWh |
| Cost saved per year | 90,618 |
| Simple payback (years) | 1.6553 |
Open this example in the calculator and change any input.
Formula
\(\Delta P = P_r\,L\left(\frac{1}{\eta_1} - \frac{1}{\eta_2}\right) \qquad \Delta E = \Delta P\,t \qquad S = \Delta E\,c_e \qquad n = \frac{C}{S}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(P_r\) | rated output | W |
| \(L\) | load factor | – |
| \(\eta_1\) | existing efficiency | – |
| \(\eta_2\) | new efficiency | – |
| \(t\) | running hours per year | s |
| \(c_e\) | energy price per kWh | currency |
| \(C\) | extra cost | currency |
| \(\Delta P\) | input power saved | W |
| \(\Delta E\) | energy saved | J |
| \(S\) | cost saved per year | currency |
| \(n\) | simple payback | years |
Method and standards
Input power is shaft power divided by efficiency; the saving is the difference at the same shaft load.
Where it is used
- Motor replacement policies.
- Energy audits.
- Choosing between rewinding and replacing.
Common mistakes
- Using nameplate efficiency at part load.
- Ignoring the higher speed of efficient motors.
- Counting hours the motor is idle.
Assumptions and limits
- Same shaft load before and after; no change in speed. Without a saving the payback is not shown.
References
- IEC 60034-30-1 (efficiency classes)
Questions and answers
What does a 55 kW motor at 75 % load gain from 92 % to 95 % efficiency?
1.42 kW less input, 11 300 kWh a year at 8000 h; at 8 per kWh that is 90 600 a year, paying back 150 000 extra in 1.7 years.
Which efficiency do I enter?
Efficiency at the actual load, from the maker's data; rewound motors are often 1–2 points below nameplate.
Does a high-efficiency motor run faster?
Slightly (less slip), which can raise fan or pump power and eat part of the saving.