Insulation Resistance: Temperature Correction, PI and DAR

Insulation resistance corrected to 40 °C, polarisation index (10 min/1 min) and dielectric absorption ratio (60 s/30 s) from megger readings.

Thermal power plantProcess steam and utilitiesElectrician and wireman licence examinations

Inputs

Examples: Motor at 30 °CWet winding at 25 °C

Results

Correction halves resistance for each 10 °C rise (IEEE 43 approximation); acceptance values are set by your standard.

1-minute reading corrected to 40 °C (MΩ)225.00
Temperature correction factor0.50000
Polarisation index R₁₀/R₁2.7778
Dielectric absorption ratio R₆₀/R₃₀1.4062

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Motor at 30 °C. The inputs, in the units selected above:

InputValue
Reading at 1 minute (MΩ)450.00 -
Reading at 10 minutes (MΩ)1,250.0 -
Reading at 30 seconds (MΩ)320.00 -
Winding temperature during the test30.000 °C

Applying the formula below gives:

ResultValue
1-minute reading corrected to 40 °C (MΩ)225.00
Temperature correction factor0.50000
Polarisation index R₁₀/R₁2.7778
Dielectric absorption ratio R₆₀/R₃₀1.4062

Open this example in the calculator and change any input.

Formula

\(R_{40} = R_T\cdot0.5^{(40 - T)/10}, \quad PI = \frac{R_{10}}{R_1}, \quad DAR = \frac{R_{60}}{R_{30}}\)

Variables

Symbol Meaning SI unit
\(R_{1}\) Reading at 1 minute (MΩ) -
\(R_{10}\) Reading at 10 minutes (MΩ) -
\(R_{30s}\) Reading at 30 seconds (MΩ) -
\(T\) Winding temperature during the test K
\(R_{40}\) 1-minute reading corrected to 40 °C (MΩ) -
\(K_T\) Temperature correction factor -
\(PI\) Polarisation index R₁₀/R₁ -
\(DAR\) Dielectric absorption ratio R₆₀/R₃₀ -

Method and standards

IEEE 43.

Where it is used

  • Motor and generator maintenance.
  • Electrician examinations.

Common mistakes

  • Testing hot without correction.
  • Comparing readings at different voltages.

Assumptions and limits

  • DC insulation test.
  • Minimum PI of 2.0 for thermal classes B, F and H and 1.5 for class A (IEEE 43); when the corrected 1-minute reading is above 5 000 MΩ the PI may not be meaningful and no PI warning is given.

References

  • IEEE Std 43-2013 (insulation resistance testing of rotating machinery): R_40 = R_T × 0.5^((40 − T)/10); PI = R₁₀/R₁; DAR = R₆₀/R₃₀

Questions and answers

450 MΩ at 1 min, 1250 at 10 min, 30 °C?

PI 2.78; corrected to 40 °C about 225 MΩ.

Why correct temperature?

Insulation resistance falls sharply as it warms.

Good PI?

Often 2 or more; your standard sets the limit by insulation class.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.