Worked example
Example: 75 kW, 94 %: 410 V, 95 A, 0.82. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Rated output of the motor | 75.000 kW |
| Rated (full-load) efficiency | 94.000 % |
| Measured line voltage | 410.00 V |
| Measured line current | 95.000 A |
| Measured power factor | 0.82000 - |
Applying the formula below gives:
| Result | Value |
|---|---|
| Measured input power √3 V I cos φ | 55.320 kW |
| Input power at full load P_r / η_r | 79.787 kW |
| Motor loading | 69.334 % |
| Estimated shaft output | 52.001 kW |
Open this example in the calculator and change any input.
Formula
\(P_{in} = \sqrt 3\, V I \cos\varphi, \quad L = \frac{P_{in}}{P_r / \eta_r}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(P_r\) | Rated output of the motor | W |
| \(\eta_r\) | Rated (full-load) efficiency | - |
| \(V\) | Measured line voltage | V |
| \(I\) | Measured line current | A |
| \(\cos\varphi\) | Measured power factor | - |
| \(P_{in}\) | Measured input power √3 V I cos φ | W |
| \(P_{in,r}\) | Input power at full load P_r / η_r | W |
| \(L\) | Motor loading | - |
| \(P_{out}\) | Estimated shaft output | W |
Method and standards
Measured input against rated input.
Where it is used
- Energy audits.
- Finding oversized motors.
Common mistakes
- Using nameplate power factor.
- Clamp reading on one phase only.
Assumptions and limits
- Balanced supply; efficiency constant with load.
References
- Input power method (Bureau of Energy Efficiency, Guide Book 3, ch. 2; US DOE Motor Challenge fact sheet)
Questions and answers
How loaded is a 75 kW motor drawing 95 A at 410 V, 0.82 power factor?
Input 55.3 kW against 79.8 kW at full load: 69 %.
Why not use current alone?
Current falls less than load because the magnetising current stays; the power method is better.
What loading is good?
Motors are most efficient around 75 % load; much below 50 % wastes energy and power factor.
Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.