Worked example
Example: 4-pole 415 V 50 Hz motor at 35 Hz. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Rated frequency of the motor | 50.000 Hz |
| Rated voltage of the motor | 415.00 V |
| Number of poles | 4.0000 - |
| Drive output frequency | 35.000 Hz |
Applying the formula below gives:
| Result | Value |
|---|---|
| Synchronous speed at that frequency | 1,050.0 rpm |
| Output voltage (constant V/f up to rated) | 290.50 V |
| Volts per hertz | 8.3000 |
| Torque available | 100.00 % |
| Power available | 70.000 % |
Open this example in the calculator and change any input.
Formula
\(N_s = \frac{2 f}{p}\ [\text{rev/s}] = \frac{120 f}{p}\ [\text{rpm}], \quad V = V_r \min\left(1, \frac{f}{f_r}\right), \quad \frac{V}{f} = \frac{V_r}{f_r}\)
\(\frac{T}{T_r} = 1\ (f \le f_r),\ \frac{f_r}{f}\ (f > f_r), \qquad \frac{P}{P_r} = \min\left(1, \frac{f}{f_r}\right)\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(f_r\) | Rated frequency of the motor | 1/s |
| \(V_r\) | Rated voltage of the motor | V |
| \(p\) | Number of poles | - |
| \(f\) | Drive output frequency | 1/s |
| \(N_s\) | Synchronous speed at that frequency | 1/s |
| \(V\) | Output voltage (constant V/f up to rated) | V |
| \(V/f\) | Volts per hertz | - |
| \(T/T_r\) | Torque available | - |
| \(P/P_r\) | Power available | - |
Method and standards
Synchronous speed and constant flux control.
Where it is used
- Setting drive frequencies.
- Checking motor capability at speed.
Common mistakes
- Expecting rated torque above base speed.
- Ignoring cooling at low speed.
Assumptions and limits
Constant torque (T/T_r = 1) below base frequency assumes the motor is cooled independently of speed. A self-cooled (shaft-fan) motor must be derated at low speed per its maker's curve; that derating is not applied. Above base frequency the voltage stays at V_r and the motor runs at constant power.
Linear V/f, no boost.
References
- N_s = 120 f / p; constant V/f control (textbook)
Questions and answers
What speed does a 4-pole motor run at 35 Hz?
Synchronous 1050 rpm (less slip), at 290.5 V on a 415 V, 50 Hz motor.
What is the V/f ratio?
8.3 V/Hz for 415 V at 50 Hz; keeping it constant keeps the flux constant.
What happens above 50 Hz?
Voltage cannot rise, so flux and torque fall: constant power.
Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.