Worked example
Example: 400/1, 1 A, TMS 0.2, SI, 4 kA. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Fault current (primary) | 4,000.0 A |
| CT ratio (primary amps per secondary amp) | 400.00 - |
| Relay pickup setting (secondary amps) | 1.0000 A |
| Time multiplier setting | 0.20000 - |
| Curve | Standard inverse (0.14, 0.02) |
Applying the formula below gives:
| Result | Value |
|---|---|
| Plug setting multiplier I_f/(CT·I_s) | 10.000 |
| Operating time | 0.59412 s |
| Time at TMS = 1 | 2.9706 s |
Open this example in the calculator and change any input.
Formula
\(PSM = \frac{I_f}{CT\cdot I_s}, \quad t = TMS\frac{k}{PSM^\alpha - 1}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(I_f\) | Fault current (primary) | A |
| \(CT\) | CT ratio (primary amps per secondary amp) | - |
| \(I_s\) | Relay pickup setting (secondary amps) | A |
| \(TMS\) | Time multiplier setting | - |
| \(\text{curve}\) | Curve | - |
| \(PSM\) | Plug setting multiplier I_f/(CT·I_s) | - |
| \(t\) | Operating time | s |
| \(t_{TMS=1}\) | Time at TMS = 1 | s |
Method and standards
Inverse-time equation.
Where it is used
- Feeder and transformer protection grading.
- Checking relay settings.
Common mistakes
- Mixing primary and secondary currents.
- Using the curve beyond 20× setting.
Assumptions and limits
- Standard IEC-type curves. A PSM above about 20 is flagged (most relays go definite-time there).
- The curve constants are the widely published IEC values (standard inverse 0.14/0.02, very inverse 13.5/1, extremely inverse 80/2, long-time inverse 120/1).
References
- Inverse-time overcurrent characteristic t = TMS·k/((I/I_s)^α − 1) with the standard inverse
- very inverse
- extremely inverse and long-time constants (IEC 60255-151 form)
Questions and answers
What is plug setting multiplier?
Fault current as a multiple of the relay's pickup current, both referred to the same side of the CT.
How are relays graded?
Each upstream relay operates 0.3–0.4 s later than the one below it at the maximum fault current both see.
What do the defaults represent?
A 400/1 CT, 1 A setting, TMS 0.2, standard inverse, 4 kA fault.
Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.