Worked example
Example: 5 A CT, 30 m of 2.5 mm², 1 VA relay, 15 VA CT. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Rated secondary current | 5.0000 A |
| One-way lead length (CT to relay or meter) | 30.000 m |
| Lead cross-section | 2.5000 mm² |
| Resistivity of the lead at its temperature | 0.022500 Ω·mm²/m |
| Burden of the relay or meter at rated current | 1.0000 VA |
| Rated burden of the CT | 15.000 VA |
Applying the formula below gives:
| Result | Value |
|---|---|
| Lead resistance, go and return | 0.54000 Ω |
| Lead burden I_s² R_L | 13.500 VA |
| Total burden | 14.500 VA |
| Share of the rated burden used | 96.667 % |
| Longest one-way lead for the rated burden | 31.111 m |
Open this example in the calculator and change any input.
Formula
\(R_L = \frac{2 \rho L}{A}, \quad S_L = I_s^2 R_L, \quad S_t = S_L + S_b\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(I_s\) | Rated secondary current | A |
| \(L\) | One-way lead length (CT to relay or meter) | m |
| \(A\) | Lead cross-section | m² |
| \(\rho\) | Resistivity of the lead at its temperature | Ω·m |
| \(S_b\) | Burden of the relay or meter at rated current | VA |
| \(S_n\) | Rated burden of the CT | VA |
| \(R_L\) | Lead resistance, go and return | Ω |
| \(S_L\) | Lead burden I_s² R_L | VA |
| \(S_t\) | Total burden | VA |
| \(u\) | Share of the rated burden used | - |
| \(L_{max}\) | Longest one-way lead for the rated burden | m |
Method and standards
Joule burden of the secondary loop.
Where it is used
- Selecting CT VA for panels and switchyards.
- Checking long CT runs.
Common mistakes
- Counting the lead one way.
- Ignoring connected meters in series.
Assumptions and limits
- Resistive burden; power factor of burdens ignored.
- A total under 25 % of the rated burden is flagged for metering CTs.
References
- Burden = I² R (IEC 61869-2 terminology)
- IEC 60364-5-52 Annex G (conductor resistivity in service)
Questions and answers
What burden do 30 m of 2.5 mm² leads add on a 5 A CT?
R = 0.54 Ω, so 13.5 VA; with a 1 VA relay 14.5 VA of a 15 VA CT.
Why use a 1 A secondary for long runs?
Lead burden goes with current squared: 25 times less than at 5 A.
Is too little burden a problem?
For metering CTs accuracy is specified between 25 % and 100 % of rated burden.
Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.