Worked example
Example: 415, 410, 400 V. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Line-to-line voltage a–b | 415.00 V |
| Line-to-line voltage b–c | 410.00 V |
| Line-to-line voltage c–a | 400.00 V |
Applying the formula below gives:
| Result | Value |
|---|---|
| Average line voltage | 408.33 V |
| Largest deviation from the average | 8.3333 V |
| Unbalance, NEMA (largest deviation ÷ average) | 2.0408 % |
| Unbalance factor, negative ÷ positive sequence | 2.1540 % |
Open this example in the calculator and change any input.
Formula
\(V_{avg} = \frac{V_{ab} + V_{bc} + V_{ca}}{3}, \quad LVUR = \frac{\Delta V_{max}}{V_{avg}}\)
\(\beta = \frac{V_{ab}^4 + V_{bc}^4 + V_{ca}^4}{(V_{ab}^2 + V_{bc}^2 + V_{ca}^2)^2}, \quad VUF = \sqrt{\frac{1 - \sqrt{3 - 6\beta}}{1 + \sqrt{3 - 6\beta}}}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(V_{ab}\) | Line-to-line voltage a–b | V |
| \(V_{bc}\) | Line-to-line voltage b–c | V |
| \(V_{ca}\) | Line-to-line voltage c–a | V |
| \(V_{avg}\) | Average line voltage | V |
| \(\Delta V_{max}\) | Largest deviation from the average | V |
| \(LVUR\) | Unbalance, NEMA (largest deviation ÷ average) | - |
| \(VUF\) | Unbalance factor, negative ÷ positive sequence | - |
Method and standards
The NEMA unbalance uses the line voltages directly. The negative-to-positive sequence ratio is computed from the three line-to-line magnitudes by the closed form above, which equals the symmetrical-component ratio (line voltages always form a closed triangle, so they have no zero sequence).
Where it is used
- Checking a supply before commissioning motors.
- Diagnosing motor overheating and nuisance trips.
- Comparing site readings with utility limits.
Common mistakes
- Using phase-to-neutral voltages, which include zero sequence.
- Comparing a NEMA figure with an IEC limit.
- Taking one reading during a transient.
Assumptions and limits
- Fundamental-frequency rms magnitudes.
- Readings taken at the same moment.
References
- NEMA MG 1 definition of voltage unbalance
- IEC 61000-4-30 / IEC 61000-2-12 negative-sequence unbalance
Questions and answers
What unbalance do 415, 410 and 400 V give?
The average is 408.3 V and the largest deviation 8.3 V: 2.0 % by NEMA. The negative-sequence ratio is 2.15 %.
Why does a small voltage unbalance matter for motors?
Negative-sequence voltage drives currents that oppose rotation; current unbalance is several times the voltage unbalance and the windings overheat.
Which definition should I use?
IEC and utility limits use the negative-sequence ratio; motor derating curves in NEMA MG 1 use the deviation from average. Use the one your limit is written in.
Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.