Worked example
Example: 100 kvar 480 V, 7 % on 415 V. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Capacitor rating at its rated voltage | 100.00 kvar |
| Capacitor rated voltage | 480.00 V |
| System voltage | 415.00 V |
| Detuning factor X_L/X_C | 7.0000 % |
| System frequency | 50.000 Hz |
Applying the formula below gives:
| Result | Value |
|---|---|
| Capacitor reactance per phase (star) | 2.3040 Ω |
| Reactor reactance | 0.16128 Ω |
| Reactor inductance | 0.51337 mH |
| Tuning frequency | 188.98 Hz |
| Tuning order | 3.7796 |
| Effective output at system voltage | 80.377 kvar |
| Voltage across the capacitor | 446.24 V |
Open this example in the calculator and change any input.
Formula
\(X_L = pX_C, \quad n_r = \frac{1}{\sqrt p}, \quad Q_{eff} = \frac{V_s^2}{X_C - X_L}, \quad V_{cap} = \frac{V_s}{1 - p}, \quad L = \frac{X_L}{2\pi f}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(Q_C\) | Capacitor rating at its rated voltage | var |
| \(V_C\) | Capacitor rated voltage | V |
| \(V_s\) | System voltage | V |
| \(p\) | Detuning factor X_L/X_C | - |
| \(f\) | System frequency | 1/s |
| \(X_C\) | Capacitor reactance per phase (star) | Ω |
| \(X_L\) | Reactor reactance | Ω |
| \(L\) | Reactor inductance | H |
| \(f_r\) | Tuning frequency | 1/s |
| \(n_r\) | Tuning order | - |
| \(Q_{eff}\) | Effective output at system voltage | var |
| \(V_{cap}\) | Voltage across the capacitor | V |
Method and standards
Series LC relations.
Where it is used
- Automatic power factor correction panels.
- Sites with VFDs and rectifiers.
Common mistakes
- Using 480 V capacitors at full nameplate kvar on 415 V.
- Choosing p without a harmonic survey.
Assumptions and limits
- Three-phase star equivalent.
- A capacitor voltage V_s/(1 − p) above the capacitor's rated voltage is flagged.
References
- Series LC detuning: n_r = 1/√p
- V_cap = V/(1 − p) (power factor correction practice)
Questions and answers
Why detune a capacitor bank?
Plain capacitors can resonate with the supply at a harmonic and amplify it; a series reactor shifts the bank's resonance below the lowest harmonic present.
Why does the capacitor see more voltage?
The reactor's voltage is in opposition, so the capacitor voltage rises by 1/(1 − p).
What do the defaults represent?
A 100 kvar, 480 V capacitor with a 7 % reactor on a 415 V, 50 Hz system.
Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.