Worked example
Example: Office loads, 70 % 3rd. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Fundamental phase current | 100.00 A |
| 3rd harmonic share | 70.000 % |
| 9th harmonic share | 15.000 % |
| 15th harmonic share | 5.0000 % |
Applying the formula below gives:
| Result | Value |
|---|---|
| Phase rms current (triplens and fundamental) | 123.09 A |
| Neutral rms current | 215.29 A |
| Neutral-to-phase ratio | 1.7491 |
Open this example in the calculator and change any input.
Formula
\(I_N = 3\sqrt{I_3^2 + I_9^2 + I_{15}^2}, \quad I_{ph} = \sqrt{I_1^2 + I_3^2 + I_9^2 + I_{15}^2}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(I_1\) | Fundamental phase current | A |
| \(I_3/I_1\) | 3rd harmonic share | - |
| \(I_9/I_1\) | 9th harmonic share | - |
| \(I_{15}/I_1\) | 15th harmonic share | - |
| \(I_{ph}\) | Phase rms current (triplens and fundamental) | A |
| \(I_N\) | Neutral rms current | A |
| \(I_N/I_{ph}\) | Neutral-to-phase ratio | - |
Method and standards
Triplen addition.
Where it is used
- Neutral conductor sizing.
- Commercial and IT installations.
Common mistakes
- Sizing neutral at half phase for non-linear loads.
- Assuming unbalance is the cause.
Assumptions and limits
The phase rms current includes only the fundamental and the triplen harmonics entered. Real rectifier currents also carry 5th, 7th, 11th … harmonics, which raise the phase current but cancel in the neutral, so the neutral-to-phase ratio shown is an upper value.
Balanced single-phase loads.
References
- Triplen harmonic addition in the neutral
- I_N = 3√ΣI_3k² (power quality definitions)
Questions and answers
Why can neutral current exceed phase current?
Triplen harmonics are in phase in all three phases and add in the neutral instead of cancelling.
Which loads cause it?
Single-phase rectifier loads: computers, LED drivers, UPS inputs; 3rd harmonic can reach 70–80 % of fundamental.
What do the defaults represent?
Office loads with 70 % third harmonic on 100 A phases.
Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.